background image

506694-01

Issue 1720

Page 16 of 16

6.  Inspect drain holes in coil compartment base and 

clean if necessary.

NOTE: 

If  insufficient  cooling  occurs,  the  unit  should  be 

gauged and refrigerant charge should be checked.

Outdoor Coil

Clean  and  inspect  outdoor  coil  (may  be  flushed  with  a 

water hose). Ensure power is off before cleaning.

NOTE: 

It  may  be  necessary  to  flush  the  outdoor  coil 

more frequently if it is exposed to substances which are 

corrosive or which block airflow across the coil (e.g., pet 

urine, cottonwood seeds, fertilizers, fluids that may contain 

high levels of corrosive chemicals such as salts) 

Sea Coast 

— Moist air in ocean locations can carry salt, 

which is corrosive to most metal. Units that are located near 

the ocean require frequent inspections and maintenance. 

These inspections will determine the necessary need 

to wash the unit including the outdoor coil. Consult your 

installing contractor for proper intervals/procedures for 

your geographic area or service contract.

Indoor Unit

1. 

Clean or change filters.

2.  Some blower motors are pre-lubricated and 

permanently sealed. No more lubrication is needed.

3.  Adjust blower speed for cooling. Measure the pressure 

drop over the coil to determine the correct blower 

CFM. Refer to the unit information service manual for 

pressure drop tables and procedure.

4.  Belt Drive Blowers - Check belt for wear and proper 

tension.

5.  Check all wiring for loose connections.
6.  Check for correct voltage at unit. (blower operating)
7.  Check amp draw on blower motor.

Motor Nameplate:_________ Actual:__________.

Indoor Coil

1.  Clean coil if necessary.

2.  Check connecting lines, joints and coil for evidence of 

oil leaks.

3.  Check condensate line and clean if necessary.

Start-Up and Performance Checklist

Job Name: ______________________________________________

Job No. _________________ Date: ________________

Job Location: ____________________________________________

City: ____________________ State: ________________

Installer: ________________________________________________

City: ____________________ State: ________________

Unit Model No. ___________________________________________

Serial No. _______________________________________

Service Technician: _______________________________________

Nameplate Voltage: _______________________________

Rated Load Ampacity: _______________

Compressor Amperage: _________________ Outdoor Fan: _____________________

Maximum Fuse or Circuit Breaker: ____________________________

Electrical Connections Tight? 

Indoor Filter Clean?

Supply Voltage (Unit Off): __________________________

Indoor Blower RPM: ______________________________________

S.P. Drop Over Indoor (Dry): ________________________

Outdoor Coil Entering Air Temperature: _______________________

Voltage with Compressor Operating: 

___________________

Outdoor Fan Checked?

Refrigerant Lines:

Leak Checked?

Properly Insulated?

Service Valves:

Fully Opened?

Caps Tight?

Thermostat

Calibrated?

Properly Set?

Level?

Summary of Contents for 13ACD-018-230

Page 1: ...rged with dry nitrogen The unit is intended for installation in existing HCFC 22 systems Carefully follow all installation procedures Open both service valves to evacuate system This unit is construct...

Page 2: ...ce included with outdoor unit or thermal expansion valve TXV See the 13ACD product specification sheet for approved fixed orifice sizes and expansion valve kit match ups Important The air conditioning...

Page 3: ...K SEATED OPENED BALL SHOWN CLOSED SERVICE PORT CORE TO INDOOR UNIT TO OUTDOOR UNIT TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 TO CLOSE ROTATE STEM CLOCKWISE 90 SERVICE PORT SERVICE PORT CAP STEM CAP VALV...

Page 4: ...rnal pressure relief valve Compressor has internal vacuum protection that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction p...

Page 5: ...ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES Clearance to one of the other three sides must be 36 inches 914mm Clearance to one of the remaining two sides may be 12 inches 305mm and the final side may be 6...

Page 6: ...ides information on replacement of existing line set If replacement line set is not required then proceed to Brazing Connections on Page 7 Refrigerant Line Set Field refrigerant piping consists of liq...

Page 7: ...ay result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING Allow braze joint to cool before removing the wet rag from the service valve Temp...

Page 8: ...OM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AN...

Page 9: ...RVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper...

Page 10: ...H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN LI...

Page 11: ...d end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line o...

Page 12: ...unit A trace amountis a maximum of two ounces 57 g refrigerant or three pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the valve on the high pressure side of the manifold gauge set...

Page 13: ...nnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury wi...

Page 14: ...HERMOSTAT 5 FEET 1 5M CHECK EXISTING ROOM THERMOSTAT Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is locat...

Page 15: ...system using evacuating procedure provided in this instruction 3 Use nitrogen to break the vacuum and install a new filter drier in the system 4 Evacuate the system again using evacuating procedure p...

Page 16: ...per tension 5 Check all wiring for loose connections 6 Check for correct voltage at unit blower operating 7 Check amp draw on blower motor Motor Nameplate _________ Actual __________ Indoor Coil 1 Cle...

Reviews: