background image

506694-01

Issue 1720

Page 14 of 16

Electrical

In the U.S.A., wiring must conform with current local codes 

and the current National Electric Code (NEC). In Canada, 

wiring must conform with current local codes and the 

current Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions 

for additional wiring application diagrams and refer to unit 

nameplate for minimum circuit ampacity and maximum  

overcurrent protection size.

24VAC Transformer

Use the transformer provided with the furnace or air handler 

for low-voltage control power (24VAC - 40 VA minimum).

SERVICE

DISCONNECT

SWITCH

MAIN FUSE BOX/

BREAKER PANEL

Refer to the unit nameplate for minimum circuit ampacity, and maximum

fuse or circuit breaker (HACR per NEC). Install power wiring and properly

sized disconnect switch.

NOTE — Units are approved for use only with copper conductors.

Ground unit at disconnect switch or to an earth ground.

SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH

NOTE — 24VAC, Class II circuit connections are made in the control

panel.

Ensure that  existing  room  thermostat  is  installed  on  an  inside  wall

approximately in the center of the conditioned area and 5 feet (1.5m) from

the floor. It should not be installed on an outside wall or where it can be

affected by sunlight or drafts.

THERMOSTAT

5 FEET

(1.5M)

CHECK EXISTING ROOM THERMOSTAT

Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a

cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.

HIGH VOLTAGE

FIELD WIRING

LOW VOLTAGE

FIELD WIRING

FACTORY

WIRING

WIRE RUN LENGTH

AWG#   INSULATION TYPE

LESS THAN 100' (30 METERS)

18      TEMPERATURE RATING

MORE THAN 100' (30 METERS) 16       35ºC MINIMUM.

Use existing or replace low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.

HIGH VOLTAGE / GROUND WIRES

CONTROL WIRING

A

Run 24VAC control wires through hole with grommet and secure with provided wire tie.

B

Make 24VAC thermostat wire connections. Locate the two wires from the contactor and make connection using field provided wire nuts:

Black to Y1
Black to C (common)

NOTE — For proper voltages, select thermostat wire (control wires)

gauge per table below

.

NOTE — Wire tie provides low voltage control wire

strain  relief  and  to  maintain  separation  of  field

installed low and high voltage circuits.

W1

Y

G

C

R

Y

G

C

THERMOSTAT

INDOOR UNIT

POWER

HEAT

COOLING

INDOOR

BLOWER

COMMON

OUTDOOR

UNIT

Y1

C

W

R

TYPICAL LOW VOLTAGE CONTROL

WIRING

SINGLE PHASE

NOTE — Do not bundle any excess 24VAC control wires inside

control panel.

CONTROL

WIRING

HIGH VOLTAGE

CONNECTIONS

(CONTACTOR)

GROUND

GROMMET AND

WIRE TIE

HIGH VOLTAGE

FLEXIBLE CONDUIT

A

B

BLACK

BLACK

Summary of Contents for 13ACD-018-230

Page 1: ...rged with dry nitrogen The unit is intended for installation in existing HCFC 22 systems Carefully follow all installation procedures Open both service valves to evacuate system This unit is construct...

Page 2: ...ce included with outdoor unit or thermal expansion valve TXV See the 13ACD product specification sheet for approved fixed orifice sizes and expansion valve kit match ups Important The air conditioning...

Page 3: ...K SEATED OPENED BALL SHOWN CLOSED SERVICE PORT CORE TO INDOOR UNIT TO OUTDOOR UNIT TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 TO CLOSE ROTATE STEM CLOCKWISE 90 SERVICE PORT SERVICE PORT CAP STEM CAP VALV...

Page 4: ...rnal pressure relief valve Compressor has internal vacuum protection that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction p...

Page 5: ...ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES Clearance to one of the other three sides must be 36 inches 914mm Clearance to one of the remaining two sides may be 12 inches 305mm and the final side may be 6...

Page 6: ...ides information on replacement of existing line set If replacement line set is not required then proceed to Brazing Connections on Page 7 Refrigerant Line Set Field refrigerant piping consists of liq...

Page 7: ...ay result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING Allow braze joint to cool before removing the wet rag from the service valve Temp...

Page 8: ...OM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AN...

Page 9: ...RVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper...

Page 10: ...H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN LI...

Page 11: ...d end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line o...

Page 12: ...unit A trace amountis a maximum of two ounces 57 g refrigerant or three pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the valve on the high pressure side of the manifold gauge set...

Page 13: ...nnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury wi...

Page 14: ...HERMOSTAT 5 FEET 1 5M CHECK EXISTING ROOM THERMOSTAT Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is locat...

Page 15: ...system using evacuating procedure provided in this instruction 3 Use nitrogen to break the vacuum and install a new filter drier in the system 4 Evacuate the system again using evacuating procedure p...

Page 16: ...per tension 5 Check all wiring for loose connections 6 Check for correct voltage at unit blower operating 7 Check amp draw on blower motor Motor Nameplate _________ Actual __________ Indoor Coil 1 Cle...

Reviews: