4
4. The capture window ends automatically, 30 seconds after pressing the Configuration Button. If you want to bind/unbind more
sensors, repeat steps 1-3.
Using the LMIO with LMCS
LMIO-101 inputs may also be used to drive Scene behaviors as well
as network group actions in conjunction with a Segment Manager.
Access with LMCS-100 is required for both. Discover the LMIO-101
using LMCS and access the button input properties table to make
these changes.
Button Type
can be set to “Load”, “Network”, or “Scene1” through
“Scene16”. Button mode can be set to “Toggle non tracking” in
order to drive network group behavior using Segment Manager
programming.
SWITCH SETTINGS
When using dry contact closure inputs they may also be configured to send out DLM commands rather than just turn loads
ON
(0) and
OFF
(X). This is accomplished by setting the DIP switches in various ways.
DIP Switch
#1 #2
#3 #4
INPUT TERMINAL FUNCTIONS
Input 1A
Input 1B
Input 2A
Input 2B
Off Off Off Off On
On
On Off Off Off After Hours
Key-Switch
Shed
N/A
Off On Off Off After Hours
Key-Switch
Clean
N/A
On On Off Off After Hours
Key-Switch
Force-On
N/A
Off Off On Off After Hours
Key-Switch
Force-Off
N/A
On Off On Off Shed
Key-Switch
Force-On
N/A
Off On On Off Shed
Key-Switch
Clean
N/A
On On On Off Shed
Key-Switch
Shed
N/A
Off Off Off On Clean
Key-Switch
Force-On
N/A
On Off Off On Clean
Key-Switch
Force-Off
N/A
Off On Off On Force-On
Key-Switch
Force-Off
N/A
#5
#6
#7
#8
#5 On inverts the input from 0-24VDC to 24VDC-0 (On) for input 1A.
#6 On inverts the input from 0-24VDCto 24VDC-0 (On) for input 2A.
#7 See “Load Binding to Inputs”
#8 See “Load Binding to Inputs” and “Isolated Relay Binding”
Command Prioritization Heirarchy and Description
The commands sent out are basic
ON/OFF
commands with different priorities. The higher priority command overrides lower priority
commands given by the system. Below is the list of priorities for these commands. For example: a Force-On (highest priority) command
overrides any
OFF
command given by any device in the system making sure that the lights remain on. When the Force-
ON
command is
released, the next highest priority command is followed.
Highest Priority
Force-On
action = Load(s)
ON
Force-Off
action = Load(s)
OFF
Clean action
= Load(s)
ON
NOTE:
Clean will turn bound loads
ON
regardless of the occupancy.
After Hours
action = Puts the load into After Hours mode where individual load parameters switch to the assigned After Hours
parameters of that load. These parameters can be different than the normal hours mode parameters. For example, Blink warning
may be active in After Hours for the load but not active in normal hours. After Hours parameters are programmed via the LMCS-100
application or through network systems where a Segment Manager or BACnet BAS is used to set After Hours schedules for a load or
device.
Key-Switch
action = Does not allow control from any of the wall switches in the DLM local network.
Lowest Priority
The exception is the Key-switch command that puts the entire system into Key-switch mode where no DLM wall switches can control
any loads. When the command is released, the system returns to normal operation so that DLM switches again control loads. Individual
switch stations can be set to ignore this message using LMCS, enabling a subset of switches in a room to stay active. A typical use for
this is to keep switches in secure locations active while disabling other publicly accessible switches.
1 2 3 4 5 6 7 8
O N
D I P
ON (0) OFF (X)
Special Usage
Input Configuration
#1, #2, #3, #4
Default:
All OFF