2

MOUNTING AND WIRING

Installation shall be in accordance with all applicable regulations, wiring practices, and codes. 

Connect to a Class 2 power source only. 

•  Class 2 Device Wiring Only. – Do Not Reclassify and Install as Class 1, 3 or Power and Lighting 

Wiring. 

•  Wire connections shall be rated suitable for the wire size (lead and building wiring) employed.

The LMIO-101 is UL2043 Plenum rated.
All connections to the LMIO-101 are Class 2 low voltage.
If code requires that the LMIO-101 be mounted in an enclosure, it can be mounted inside a 4” x 4” 

junction box, inside a 21/8” deep (or deeper) 2-gang wall box, in a 3” or 4” octagonal box, or on a din 

rail inside a panel. 

Attach the LMRJ Cable

The DLM local network uses free topology low voltage wiring. The LMIO-101 can connect anywhere on the DLM local network.

RJ45 ports (2)

Configuration 

push button

LEDs (5)

DIP switches

Input/Output

Wiring Terminals

Configuration LED

Attach din rail clip

Option 1: Attach to din rail

Option 2: Mount to wall

Inside a 2-gang J-box

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 – IT MAY 

DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

LMRJ Cables

Line Voltage

Room

Controller

Occupancy Sensor

Switch

LMIO-100 Series Digital

Input/Output Interface

Low Voltage Wires (2-10)

Loads

1

2

Input from Third Party Device

(example: time clock)

Output to Third Party Device 

(example: HVAC)

(3) N.C.

(normally closed)

(1) N.O.

(normally open)

To External

Device

Contacts rated at 1 amp @ 24V AC/DC

Isolated Relay

LMIO-101 Terminals

(2) COM

The isolated relay output is on 

terminals 1, 2 and 3. By default, the 

relay responds to a signal from any 

DLM sensor. See 

Isolated Relay 

Binding

 to change bound sensors.

Momentary Push Button Switch

LMIO-101 Terminals

 

ON

OFF

(5) +24VDC

(6) Input 1A

(8) Input 2A

or

(7) Input 1B

(9) Input 2B

or

NOTE: 

This is a toggling input

Press once

 = signal sent, the 

Blue LED corresponding to the 

input will be lit on the LMIO-101

Press again

 = the relinquish 

command is sent, the Blue LED 

corresponding to the input will be 

OFF on the LMIO-101

Momentary On/Momentary Off Switch

LMIO-101 Terminals

 

ON

OFF

(5) +24VDC

(6) Input 1A

(8) Input 2A

or

(7) Input 1B

(9) Input 2B

or

Contact Closure Options

(6, 7, or 8)

Input 1A, 1B or 2A

24VDC

from

3rd Party

Source

+

-

(5) +24VDC

(6, 7, or 8)

Input 1A, 1B or 2A

(4) Ground GND

LMIO-101 Terminals

TERMINAL CONNECTIONS

Summary of Contents for Wattstopper LMIO-101

Page 1: ...ates on power from the DLM local network It contains a 24VDC isolated relay single pole double throw with normally open N O normally closed N C and common outputs for output to other systems It also provides input terminal connections and options for converting input signals from 3rd party devices into load controlling messages for the DLM system Outputs Isolated Relay 24VDC Pilot Light The isolat...

Page 2: ... CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT LMRJ Cables Line Voltage Room Controller Occupancy Sensor Switch LMIO 100 Series Digital Input Output Interface Low Voltage Wires 2 10 Loads 1 2 Input from Third Party Device example time clock Output to Third Party Device example HVAC 3 N C normally closed 1 N O normally open To External Devic...

Page 3: ...turns OFF to indicate the input is no longer bound to the load that is currently ON To bind the input to the load that is currently ON activate the input using the third party switch or dry contact closure The input s blue LED lights indicating that it controls the load that is currently ON NOTE If you can not activate the third party switch or the dry contact closure you can still bind Input 1 an...

Page 4: ...itization Heirarchy and Description The commands sent out are basic ON OFF commands with different priorities The higher priority command overrides lower priority commands given by the system Below is the list of priorities for these commands For example a Force On highest priority command overrides any OFF command given by any device in the system making sure that the lights remain on When the Fo...

Page 5: ... exceed the Shed Level When the contact input opens lights will return to their values prior to the Shed command TROUBLESHOOTING Relay does not close when the room is occupied 1 Check that the circuit breaker is ON 2 Make sure that there is an occupancy sensor detecting occupancy 3 Check all wiring connections 4 Check for 24VDC input to the LMIO 101 Plug in a different DLM device at the LMIO 101 l...

Page 6: ...e undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and...