TESTING THE FSP-301B WITH THE SENSOR CONFIG APP

1.  The first time the sensor is installed and powered, there will be 50 seconds of warm-up. The load will turn OFF after the warm-up 

time if no motion is detected. To test functionality further, proceed to steps below

2.  Log in to the Sensor Config App, then tap 

Device Discovery

. The 

Devices

 screen opens and displays a list of sensors along with 

their signal strength.

3.  Tap a sensor. The loads connected to that sensor will flash ON and OFF, to give a visual indication of which sensor you are 

communicating with. After a few seconds, the 

Device Security

 screen opens.

4.  Turn the 

Select Jobsite

 switch Off. 

This allows you to test the sensor 

without having to store a password in 

the sensor. Than tap 

Submit

.

5.  Tap the 

Controls

 option. The 

parameters on this page are used for 

testing the sensor. Additionally, the 

current amount of light registered by 

the light level sensor, as well as the 

sensor’s firmware version is displayed. 

6.  Tap 

Test Mode

. This mode shortens 

timeouts for High/Low and Cut Off, 

to allow quick verification of settings. 

You can set the length for test mode 

(default is 3 minutes). Range: 1 to 5 minutes. Tap Start to enter test mode.

7.  If you tap 

Dimmer Level

, the screen shows the current dimming level (from 0V to 10V). You can temporarily change the dimming 

level for testing purposes by dragging the slider or tapping the “+” or “–” buttons. The level will change to the specified amount for 

several seconds, then revert to the previous amount.

TROUBLESHOOTING

Lights will not go to High Mode:

•  Check all wire connections and verify the load and the ground wires are tightly secured.
•  Make sure that the sensor is not obstructed.
•  Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness 

in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient 

light will cause the lights to be held OFF. See the new settings section for instructions.

•  If lights still do not turn ON, call 800.879.8585 for technical support.

Lights will not go into Low Mode:

•  The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the 

desired delay and that there is no movement within the sensor’s view for that time period.

•  To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5 

seconds.

•  If lights still do not fade to Low Mode, call 800.879.8585 for technical support

Lights will not turn OFF:

•  Cut Off time may be set to “Disable.”
•  Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor’s view for that time period when 

the lights are in Low Mode.

•  To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5 

seconds and then turn OFF (if cut off is enabled) after 10 sec.

•  If lights still do not turn OFF, call 800.879.8585 for technical support.

False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity 

for PIR detection.

•  If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
•  If experiencing false triggering during fade down/Off, try increasing the fade time.

Lights do not turn ON:

Check for blinking blue LED. If the LED blinks twice, the sensor has reached its Hold Off setpoint, if the LED blinks 3 times, the sensor 

has reached it’s Photocell Light Level setpoint. 

Lights suddenly turn off and will not come back on:

Check for blinking blue LED. If the LED blinks twice, the sensor has reached its Hold Off setpoint, if the LED blinks 3 times, the sensor 

has reached its Photocell Light Level setpoint. 

Turn Select Jobsite Off

Select Controls

Controls Menu for Testing

Summary of Contents for Wattstopper FSP-301B

Page 1: ...usly raise or lower the dimming level of the lighting loads based on the ambient light and desired light level setting The FSP 301B operates at 12 32 VDC It is designed to be installed in indoor and o...

Page 2: ...face of the fixture If needed add the nut between the sensor body and the rubber gasket to ensure a secure fit Install the nipple nut securely against the fixture to a torque of 25 30 in lbs to ensure...

Page 3: ...TE Bluetooth communication ranges can vary depending on the device as well as mobile carrier Wattstopper recommends devices with Bluetooth 5 0 Iphone 8 and Samsung Galaxy S8 and later devices are reco...

Page 4: ...setpoint needs to be adjusted If set for minimum more than 1 fc at the sensor of ambient light will cause the lights to be held OFF See the new settings section for instructions If lights still do not...

Page 5: ...digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment...

Page 6: ...e fixation suspendu pour l installation sur un poteau ou sur un luminaire Le d tecteur utilise la technologie de d tection par infrarouge passif IRP qui r agit aux changements dans l nergie infrarouge...

Page 7: ...en caoutchouc au raccord et installez le d tecteur face vers le bas Assurez vous que le joint en caoutchouc touche la surface du luminaire Si n cessaire ajoutez l crou entre le corps du d tecteur et...

Page 8: ...ppareils iOS et Android Rechercher Wattstopper Sensor Config sur votre appareil pour le t l charger REMARQUE La qualit du signal et la distance de communication Bluetooth peuvent varier en fonction de...

Page 9: ...haut V rifiez toutes les connexions et la charge et assurez vous que les fils de terre sont bien fix s Assurez vous que le d tecteur n est pas obstru V rifiez le param tre du niveau de luminosit pour...

Page 10: ...ous tension il se produit un pr chauffage de 50 secondes La charge s teindra apr s le temps de pr chauffage si aucun mouvement n est d tect RENSEIGNEMENTS POUR COMMANDES Num ro de Catalogue Descriptio...

Page 11: ...tilisateur doivent tre maintenu en tout temps Tout changement ou modification non express ment approuv par The Watt Stopper Inc pourrait annuler le droit de l utilisateur utiliser l quipement D CLARAT...

Page 12: ...boquilla detr s El FSP 301B D posee una boquilla de montaje de ca da para montar en un polo o en la luminaria Los sensores usan tecnolog a de detecci n de infrarrojo pasivo PIR que reacciona a los ca...

Page 13: ...de 22 mm 0 875 de di metro a trav s del polo 3 Agregue la empaque de goma a la boquilla e instale el sensor boca abajo Aseg rese de que la empaque de goma toque la superficie de la luminaria Si es ne...

Page 14: ...el sensor est disponible para dispositivos iOS y Android Busque Wattstopper Sensor Config en su dispositivo para descargar NOTA Los rangos de comunicaci n Bluetooth pueden variar seg n el dispositivo...

Page 15: ...s luces no pasan al Modo alto Controle todas las conexiones de cables y verifique la carga y que los cables de regulaci n est n bien ajustados Aseg rese de que el sensor no est bloqueado Controle el p...

Page 16: ...entamiento La carga se apagar despu s del tiempo de calentamiento si no se detecta movimiento INFORMACI N PARA HACER PEDIDOS N de cat logo Descripci n FSP 301B Fase simple doble universal Atenuaci n C...

Page 17: ...osici n a radiofrecuencia RF la FCC e IC para dispositivos m viles Este dispositivo solo est autorizado para su uso en una aplicaci n m vil Al menos 20 cm de distancia de separaci n entre este disposi...

Page 18: ...18...

Page 19: ...19...

Page 20: ...on ou la performance de ce produit ou tout autre dommage indirect li la perte de propri t de revenus ou de profits ou aux co ts d enl vement d installation ou de r installation WattStopper garantiza q...

Reviews: