4
TESTING THE FSP-301B WITH THE SENSOR CONFIG APP
1. The first time the sensor is installed and powered, there will be 50 seconds of warm-up. The load will turn OFF after the warm-up
time if no motion is detected. To test functionality further, proceed to steps below
2. Log in to the Sensor Config App, then tap
Device Discovery
. The
Devices
screen opens and displays a list of sensors along with
their signal strength.
3. Tap a sensor. The loads connected to that sensor will flash ON and OFF, to give a visual indication of which sensor you are
communicating with. After a few seconds, the
Device Security
screen opens.
4. Turn the
Select Jobsite
switch Off.
This allows you to test the sensor
without having to store a password in
the sensor. Than tap
Submit
.
5. Tap the
Controls
option. The
parameters on this page are used for
testing the sensor. Additionally, the
current amount of light registered by
the light level sensor, as well as the
sensor’s firmware version is displayed.
6. Tap
Test Mode
. This mode shortens
timeouts for High/Low and Cut Off,
to allow quick verification of settings.
You can set the length for test mode
(default is 3 minutes). Range: 1 to 5 minutes. Tap Start to enter test mode.
7. If you tap
Dimmer Level
, the screen shows the current dimming level (from 0V to 10V). You can temporarily change the dimming
level for testing purposes by dragging the slider or tapping the “+” or “–” buttons. The level will change to the specified amount for
several seconds, then revert to the previous amount.
TROUBLESHOOTING
Lights will not go to High Mode:
• Check all wire connections and verify the load and the ground wires are tightly secured.
• Make sure that the sensor is not obstructed.
• Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness
in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient
light will cause the lights to be held OFF. See the new settings section for instructions.
• If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go into Low Mode:
• The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor’s view for that time period.
• To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5
seconds.
• If lights still do not fade to Low Mode, call 800.879.8585 for technical support
Lights will not turn OFF:
• Cut Off time may be set to “Disable.”
• Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor’s view for that time period when
the lights are in Low Mode.
• To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5
seconds and then turn OFF (if cut off is enabled) after 10 sec.
• If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
• If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
• If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking blue LED. If the LED blinks twice, the sensor has reached its Hold Off setpoint, if the LED blinks 3 times, the sensor
has reached it’s Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking blue LED. If the LED blinks twice, the sensor has reached its Hold Off setpoint, if the LED blinks 3 times, the sensor
has reached its Photocell Light Level setpoint.
Turn Select Jobsite Off
Select Controls
Controls Menu for Testing