background image

2

CAUTION

WATTSTOPPER RECOMMENDS ADDING A 

20KA SURGE SUPPRESSOR TO PROTECT 

THE FIXTURE, DRIVER AND FSP SENSOR.

There are three configurations of the sensor: 

•  The FSP-301B mounts inside the fixture. 
•  The FSP-301B-S mounts to a fixture or an enclosure with a 1/2” 

knockout. 

•  The FSP-301B-D mounts to a pole or fixture.

Mounting Inside the Fixture

1.  Determine an appropriate mounting location inside the light fixture 

minimizing the electric light contribution to the sensor’s photocell. 

Allow a minimum distance of 0.2” (5.1mm) from the wiring end of 

the sensor to the wall of the fixture.

2.  Drill a hole 1.30” (33.0mm) in diameter through the sheet metal in 

the bottom of the fixture.

3.  Add the rubber gasket to the threaded collar, and install the sensor 

face down, parallel to the mounting surface. Ensure the rubber gasket 

touches the inside surface of the fixture. Install the tightening nut 

securely against the fixture to a torque of 25-30 in-lbs to ensure IP rating is maintained. 

NOTE: 

An optional collar can be installed in place of the tightening nut on the FSP-301B. This collar is included with the  

FSP-301B-S and FSP301B-D, as shown below.

Mounting to a Fixture/Enclosure – Straight Nipple

1.  Determine an appropriate mounting location minimizing the electric light contribution 

to the sensor’s photocell.

2.  If there is no knockout, drill a hole 0.875” (22mm) in diameter through the sheet 

metal in the fixture or enclosure.

3.  Add the rubber gasket to the nipple, and install the sensor face down. Ensure the 

rubber gasket touches the surface of the fixture. Install the nipple nut securely 

against the fixture to a torque of 25–30 in-lbs to ensure IP rating is maintained. 

Mounting to a Pole or Fixture – Drop Nipple 

1.  Determine an appropriate mounting location on the pole.
2.  Drill a hole 0.875” (22mm) in diameter through the pole.
3.  Add the rubber gasket to the nipple, and install the sensor face down. Ensure the 

rubber gasket touches the surface of the fixture. If needed, add the nut between 

the sensor body and the rubber gasket to ensure a secure fit. Install the nipple 

nut securely against the fixture to a torque of 25–30 in-lbs to ensure IP rating is 

maintained. 

Completing the Installation

1.  Align the locking features between the sensor and lens module and push the lens 

module forward until the o-ring seals firmly. Turn the lens module clockwise to 

ensure it locks in place.

2.  Connect wires as shown in wiring diagram.
3.  Restore power from the circuit breaker.

NOTE: 

The IP66 rating for this unit is based on proper installation as indicated above. 

However, as Fixture housings may vary in thickness, material, and hole 

dimensions to accommodate this unit, all precautions to maintain IP66 should be 

considered with the combination and installation of the unit to the Fixture Housing. 

This includes installation to an IP66 rated Fixture Housing and use of suitable 

outdoor rated silicone seals or accessories.

LENS OPTIONS

Several lenses are available for use with the FSP-301B. Lenses give coverage at mounting heights between 8’–40’ for applications 

such as, offices, warehouses and outdoor use. Density and range of the coverage is determined by the type of lens and mounting 

height. A lens with shroud option is also available. The shroud blocks light coming from the fixture, to prevent interference with the 

photocell function of the sensor. Lens modules are IP-66 rated when combined with an FSP-301B sensor mounted to an outdoor rated 

fixture. See the FSP-Lx Coverage Guide for more information. 

Tightening Nut

(or Optional Collar)

Fixture 

Wall

Lens Assembly

Outside 

Fixture Wall

Inside Fixture

Wall

Mounting Within Fixture

Tightening Nut

(or Optional Collar)

Rubber

Gasket

Rubber

Gasket

1

2

INSTALLATION

WARNING

TURN THE POWER OFF AT THE CIRCUIT BREAKER 

BEFORE INSTALLING THE SENSOR.

Straight Nipple Mount

Nipple

Rubber 

Gaskets

Nipple

Nut

Drop Nipple Mount

Nipple

Nut

Nipple

Rubber 

Gaskets

Drop Nipple Mount

Nipple

Rubber 

Gaskets

Nipple

Nut

Nut

NOTE: 

The Outside Fixture Wall thickness should be 

no greater than 0.125” (3.18mm) for optimal 

sensor mounting and security.

Summary of Contents for Wattstopper FSP-301B

Page 1: ...usly raise or lower the dimming level of the lighting loads based on the ambient light and desired light level setting The FSP 301B operates at 12 32 VDC It is designed to be installed in indoor and o...

Page 2: ...face of the fixture If needed add the nut between the sensor body and the rubber gasket to ensure a secure fit Install the nipple nut securely against the fixture to a torque of 25 30 in lbs to ensure...

Page 3: ...TE Bluetooth communication ranges can vary depending on the device as well as mobile carrier Wattstopper recommends devices with Bluetooth 5 0 Iphone 8 and Samsung Galaxy S8 and later devices are reco...

Page 4: ...setpoint needs to be adjusted If set for minimum more than 1 fc at the sensor of ambient light will cause the lights to be held OFF See the new settings section for instructions If lights still do not...

Page 5: ...digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment...

Page 6: ...e fixation suspendu pour l installation sur un poteau ou sur un luminaire Le d tecteur utilise la technologie de d tection par infrarouge passif IRP qui r agit aux changements dans l nergie infrarouge...

Page 7: ...en caoutchouc au raccord et installez le d tecteur face vers le bas Assurez vous que le joint en caoutchouc touche la surface du luminaire Si n cessaire ajoutez l crou entre le corps du d tecteur et...

Page 8: ...ppareils iOS et Android Rechercher Wattstopper Sensor Config sur votre appareil pour le t l charger REMARQUE La qualit du signal et la distance de communication Bluetooth peuvent varier en fonction de...

Page 9: ...haut V rifiez toutes les connexions et la charge et assurez vous que les fils de terre sont bien fix s Assurez vous que le d tecteur n est pas obstru V rifiez le param tre du niveau de luminosit pour...

Page 10: ...ous tension il se produit un pr chauffage de 50 secondes La charge s teindra apr s le temps de pr chauffage si aucun mouvement n est d tect RENSEIGNEMENTS POUR COMMANDES Num ro de Catalogue Descriptio...

Page 11: ...tilisateur doivent tre maintenu en tout temps Tout changement ou modification non express ment approuv par The Watt Stopper Inc pourrait annuler le droit de l utilisateur utiliser l quipement D CLARAT...

Page 12: ...boquilla detr s El FSP 301B D posee una boquilla de montaje de ca da para montar en un polo o en la luminaria Los sensores usan tecnolog a de detecci n de infrarrojo pasivo PIR que reacciona a los ca...

Page 13: ...de 22 mm 0 875 de di metro a trav s del polo 3 Agregue la empaque de goma a la boquilla e instale el sensor boca abajo Aseg rese de que la empaque de goma toque la superficie de la luminaria Si es ne...

Page 14: ...el sensor est disponible para dispositivos iOS y Android Busque Wattstopper Sensor Config en su dispositivo para descargar NOTA Los rangos de comunicaci n Bluetooth pueden variar seg n el dispositivo...

Page 15: ...s luces no pasan al Modo alto Controle todas las conexiones de cables y verifique la carga y que los cables de regulaci n est n bien ajustados Aseg rese de que el sensor no est bloqueado Controle el p...

Page 16: ...entamiento La carga se apagar despu s del tiempo de calentamiento si no se detecta movimiento INFORMACI N PARA HACER PEDIDOS N de cat logo Descripci n FSP 301B Fase simple doble universal Atenuaci n C...

Page 17: ...osici n a radiofrecuencia RF la FCC e IC para dispositivos m viles Este dispositivo solo est autorizado para su uso en una aplicaci n m vil Al menos 20 cm de distancia de separaci n entre este disposi...

Page 18: ...18...

Page 19: ...19...

Page 20: ...on ou la performance de ce produit ou tout autre dommage indirect li la perte de propri t de revenus ou de profits ou aux co ts d enl vement d installation ou de r installation WattStopper garantiza q...