Alarm
A35
DIESEL MODE
Description
The UPS is supplied by the diesel generator.
Possible
causes
The auxiliary contact which activates the diesel generator
connected to the UPS is closed, and imposes this operating
mode.
Solutions
1. Wait for the diesel generator to stop as soon as the mains
voltage is restored.
2. Check the connection of the auxiliary contact which signals the
diesel generator start, to terminals XD1/XD2.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A36
DC FASTSHUTDOWN
Description
Inverter shutdown due to the operation of the protection sensor as a
result of sudden DC voltage variations.
Possible
causes
Battery fault.
Solutions
1. Check the battery.
2. Reset the system.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A38
INV --> LOAD
Description
The load is fed by the inverter. This alarm is active for UPS systems in
“ECO” mode, where the preferential supply is from the bypass line.
Possible
causes
Temporary changeover due to bypass line failure.
Solutions
1. Verify the status of the bypass line and check whether other
alarms are present.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A39
INV ERROR LOOP
Description
The control is not able to regulate the inverter voltage precisely.
Possible
causes
Regulation system failure.
Solutions
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
Summary of Contents for UPS
Page 10: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV B ...
Page 61: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMG38225 REV B 61 ...
Page 63: ......
Page 114: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV B ...
Page 142: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 140 OMG38225 REV B ...