UPS user manual
Manuel de l’utilisateur de l’ASI
Utilizzo dell’UPS
36
OMG38225 REV. B
Setting all the parameters
To save all the parameters it is necessary to reach the end of the guided procedure
until the last screen previously shown.
If the procedure is interrupted earlier, none of the parameters previously set will be
saved.
6.5
SETTING THE MODBUS PARAMETERS
The parameters regarding the communication via RS485 interface can be set in the MODBUS
menu.
Modbus address
MODBUS ADDRESS
The single digits can be modified via the arrow
keys ( / ) and confirmed by pressing
(ENTER).
202
Parameter
Standard
Range
MODBUS ADDRESS
1
1 …. 247
6.6
UPS TEST
The UPS TEST menu allows to carry out a switching test of the inverter. The inverter is switched
off and the load is transferred to the bypass supply. The inverter supply is automatically restored
after a few seconds.
UPS TEST?
The value on the second line is ready to be
changed
NO
(1x)
UPS TEST?
The parameter is changed. The change is
confirmed by pressing
(ENTER)
YES
SPECIAL
The system performs a test and returns to the
previous screen
UPS TEST
Possible loss of supply
In case of power failure while the test is being performed, the immediate operation of
the inverter is not guaranteed.
Summary of Contents for UPS
Page 10: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV B ...
Page 61: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMG38225 REV B 61 ...
Page 63: ......
Page 114: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV B ...
Page 142: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 140 OMG38225 REV B ...