9/49
Circuit breaker TX
3
6000 A
up to 63 A (1 module per pole)
Cat. N° (s) : 4 033 49 to 4 035 68, 4 037 12 to 4 037 78
5. GENERAL CHARACTERISTICS
(continued):
Coordination between modular circuit-breakers, three-phase network (+ neutal) 400 / 415 V~ according to IEC/EN 60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected
between phase and neutral under 230 V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400 V.
m.c.b. upstream
DX
3
36kA
DX
3
50kA
C Curve
B, C and D Curves
m.c.b. downstream
≤25A
32A
40A
50A
63A
80A
≤25A
32A
40A
50A
63A
TX
3
6000A
B, C & D Curves
<6A
25kA
25kA
25kA
25kA
25kA
25kA
36kA
36kA
36kA
36kA
36kA
6A
25kA
25kA
25kA
25kA
25kA
25kA
36kA
36kA
36kA
36kA
36kA
10A
25kA
25kA
25kA
25kA
25kA
25kA
36kA
36kA
36kA
36kA
36kA
13A
25kA
25kA
25kA
25kA
25kA
25kA
36kA
36kA
36kA
36kA
36kA
16A
25kA
25kA
25kA
25kA
25kA
25kA
36kA
36kA
36kA
36kA
36kA
20A
25kA
25kA
25kA
25kA
25kA
25kA
36kA
36kA
36kA
36kA
36kA
25A
-
25kA
25kA
25kA
25kA
25kA
-
36kA
36kA
36kA
36kA
32A
-
-
25kA
25kA
25kA
25kA
-
-
36kA
36kA
36kA
40A
-
-
-
25kA
25kA
25kA
-
-
-
36kA
36kA
50A
-
-
-
-
25kA
25kA
-
-
-
-
36kA
63A
-
-
-
-
-
25kA
-
-
-
-
-
According to the curves and ratings of circuit breakers, attention to the magnetic threshold and to the size of upstream circuit breakers which must
necessarily be higher.
Technical data sheet: F01547EN/01
Updated: 15/10/2014
Created: 30/05/2014