22/49
Circuit breaker TX
3
6000 A
up to 63 A (1 module per pole)
Cat. N° (s) : 4 033 49 to 4 035 68, 4 037 12 to 4 037 78
5. GENERAL CHARACTERISTICS
(continued)
Selectivity between two levels of protection
. The downstream circuit breaker must always have a magnetic threshold and a rated current lower than those of the upstream protection.
. Selectivity is indicated total (T) if there is selectivity up to the value of breaking capacity (according to IEC / EN 60947-2) of the downstream circuit
breaker.
Selectivity between modular circuit breakers and fuses:
. Selectivity limit at 400 V~: values in Ampere.
Fuse upstream
gG Type
m.c.b. downstream
32A
40A
50A
63A
80A
100A
125A
160A
TX
3
6000A
B & C Curves
<6A
1300
1900
2500
4000
4600
T
T
T
6A
1300
1900
2500
4000
4600
T
T
T
10A
-
1600
2200
3200
3600
T
T
T
13A
-
1400
1800
2600
3000
5600
T
T
16A
-
1400
1800
2600
3000
5600
T
T
20A
-
1200
1500
2200
2500
4600
T
T
25A
-
-
1300
2000
2200
4100
5500
T
32A
-
-
1200
1700
1900
3500
4500
T
40A
-
-
-
-
1700
3000
4000
T
50A
-
-
-
-
1600
2600
3500
5000
63A
-
-
-
-
-
2400
3300
5000
Fuse upstream
gG Type
m.c.b. downstream
32A
40A
50A
63A
80A
100A
125A
160A
TX
3
6000A
D Curve
<6A
1300
1900
2500
4000
4600
T
T
T
6A
1200
1600
2200
4000
42000
T
T
T
10A
-
1600
2200
3200
3600
T
T
T
13A
-
1400
1800
2600
3000
5600
T
T
16A
-
1400
1800
2600
3000
5600
T
T
20A
-
1200
1500
2200
2500
4600
T
T
25A
-
-
1200
1800
2100
3700
5000
T
32A
-
-
-
1500
1800
3000
4000
5000
40A
-
-
-
-
1700
2600
3500
4500
50A
-
-
-
-
1400
2000
3000
4000
63A
-
-
-
-
-
2000
3000
4000
. T = Total discrimination
Technical data sheet: F01547EN/01
Updated: 15/10/2014
Created: 30/05/2014