Circuit breaker TX
3
6000 A
up to 63 A (1 module per pole)
Cat. N° (s) : 4 033 49 to 4 035 68, 4 037 12 to 4 037 78
5. GENERAL CHARACTERISTICS
(continued)
Selectivity between two levels of protection
. The downstream circuit breaker must always have a magnetic threshold and a rated current lower than those of the upstream protection.
. Selectivity is indicated total (T) if there is selectivity up to the value of breaking capacity (according to IEC / EN 60947-2) of the downstream circuit
breaker.
Selectivity between modular circuit breakers and fuses:
. Selectivity limit at 400 V~: values in Ampere.
Fuse upstream
aM Type
m.c.b. downstream
25A
32A
40A
50A
63A
80A
100A
125A
160A
TX
3
6000A
B & C Curves
<6A
1000
1600
2100
3200
T
T
T
T
T
6A
1000
1600
2100
3200
T
T
T
T
T
10A
-
1100
1700
2500
5000
T
T
T
T
13A
-
1000
1400
2100
4000
T
T
T
T
16A
-
1000
1400
2100
4000
T
T
T
T
20A
-
-
1300
1800
3400
5100
T
T
T
25A
-
-
1100
1600
3000
4500
T
T
T
32A
-
-
-
1300
2400
3800
5000
T
T
40A
-
-
-
-
2100
3100
4200
T
T
50A
-
-
-
-
2000
2900
3700
T
T
63A
-
-
-
-
-
2800
3500
5500
T
Fuse upstream
aM Type
m.c.b. downstream
25A
32A
40A
50A
63A
80A
100A
125A
160A
TX
3
6000A
D Curve
<6A
900
1400
2000
2700
5500
T
T
T
T
6A
900
1400
2000
2700
5500
T
T
T
T
10A
-
1100
1700
2500
5000
T
T
T
T
13A
-
1000
1400
2100
4000
T
T
T
T
16A
-
1000
1400
2100
4000
T
T
T
T
20A
-
-
1300
1800
3400
5100
T
T
T
25A
-
-
1000
1500
2700
4000
5500
T
T
32A
-
-
-
1100
2100
3500
4700
T
T
40A
-
-
-
-
1800
2800
4000
T
T
50A
-
-
-
-
1800
2500
3500
5500
T
63A
-
-
-
-
-
2500
3500
5500
T
. T = Total discrimination
Technical data sheet: F01547EN/01
Updated: 15/10/2014
Created: 30/05/2014