13/49
Circuit breaker TX
3
6000 A
up to 63 A (1 module per pole)
Cat. N° (s) : 4 033 49 to 4 035 68, 4 037 12 to 4 037 78
5. GENERAL CHARACTERISTICS
(continued):
Coordination between modular circuit-breakers and MCCBs, three-phase network (+ neutal) 400 / 415 V~ according to
IEC/EN 60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected between
phase and neutral under 230 V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400 V.
m.c.c.b.. upstream
DPX / H / L 1250
(Thermal -magnetic)
DPX / H 1600
(electronic)
50 – 70 – 100kA
36 – 70kA
m.c.b. downstream
500 to 1250A
630 to 1600A
TX
3
6000A
B, C & D Curves
<6A
25kA
25kA
6A
25kA
25kA
10A
25kA
25kA
13A
25kA
25kA
16A
25kA
25kA
20A
25kA
25kA
25A
20kA
20kA
32A
15kA
15kA
40A
15kA
15kA
50A
12.5kA
12.5kA
63A
12.5kA
12.5kA
According to the curves and ratings of circuit breakers, attention to the magnetic (or electronic) threshold and to the size of upstream circuit
breakers which must necessarily be higher.
Technical data sheet: F01547EN/01
Updated: 15/10/2014
Created: 30/05/2014