background image

LI3000 

Uninterruptible Power Supplies

 

 

 

13 

 

Model 

LI3000 

Capacity    (VA) 

3000VA 

Capacity    (Watts) 

2200W 

Input   

    Voltage Range 

85 – 150Vac 

    Frequency Range   

47 – 63Hz     

Output 

    On Battery Output Voltage   

Pure Sine Wave at /- 5% 

 

    On Battery Output 

Frequency   

60 Hz   

    Transfer Time (Typical) 

4ms 

    Overload Protection 

On Utility: Circuit Breaker, On Battery: Internal Current Limiting 

Surge Protection and Filtering 

    Lightning / Surge Protection 

Yes 

    Internet Ready 

Yes 

Physical 

    Total # of UPS Receptacles 

    Maximum Dimensions 

2U Rack * 2 

    Weight (lbs) 

122.5 

Battery 

    Sealed Maintenance Free 

Lead Acid Battery   

7AHx8 

    Typical Recharge Time 

8 Hours 

Warning Diagnostics 

    Indicators 

Power On, Using Battery, AVR, Load Level, Battery Level 

    Audible Alarms 

On Battery, Low Battery, Overload 

Environmental 

Operating Temperature 

+ 32°F to 95°F (0°C to 35°C) 

Operating Relative Humidity 

0 to 95% NON-CONDENSING 

Communication 

    SeeUPS2020 Software 

Windows 98/ME/NT/2000/XP, Mac OS 10.0 or later 

Management 

    Self-Test 

Manual Self-Test 

    Auto-Charger 

Yes 

    Auto-Restart 

Yes 

    USB 

Yes 

    SNMP / HTTP Network 

Optional 

TECHNICAL SPECIFICATIONS 

Summary of Contents for Lineage LI3000

Page 1: ...User s Manual Lineage LI3000 UPS K01 1120005 00...

Page 2: ...E POWER REQUIREMENTS OF YOUR EQUIPMENT 4 TO ESTIMATE POWER REQUIREMENTS 5 HARDWARE INSTALLATION 5 BASIC OPERTAION 8 FRONT PANEL DESCRIPTION 8 REAR PANEL DESCRIPTION 9 TROUBLESHOOTING 12 TECHNICAL SPEC...

Page 3: ...remove the risk Voltage may still be present from the battery pack The battery pack quick connectors should be disconnected before performing maintenance or service work on the UPS When replacing the...

Page 4: ...ower supplied outlets does not exceed the UPS unit s rated capacity 3000VA 2200W for LI3000 If rated unit capacities are exceeded an overload condition may occur and cause the UPS unit to shut down or...

Page 5: ...eceipt However recharging the battery for at least four hours is recommended to insure that the batteries are fully charged Charge loss may occur during shipping and storage To recharge the battery si...

Page 6: ...indicator light will illuminate 7 Your UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically recharge 8 To maintain optimal battery char...

Page 7: ...LI3000 Uninterruptible Power Supplies 7 Figure 1 Connecting LI3000 with Battery Pack...

Page 8: ...it returns to on line operation If the UPS fails the self test please recharge the battery for 4 hours and perform another self test If it fails after recharging the battery please replace the batter...

Page 9: ...the UPS outlets are providing clean power free of surges and spikes Battery Indicator This illuminates during utility failure indicating that the battery is supplying power to the battery power suppl...

Page 10: ...insures uninterrupted operation of connected equipment during a power failure NOTE When the UPS is overloaded the other six minor outlets will not provide power to equipments prior to the Individual B...

Page 11: ...shutdown User Control delay can be set in the SeeUPS2020 Plus software Recommended time is 5 minutes Once the Primary computer is shutdown the UPS will signal the Secondary computer and initiate the...

Page 12: ...seconds and then turn the UPS on The unit is not connected to an AC outlet The unit must be connected to a110 120V 50 60Hz outlet The battery is worn out Contact Legacy Power Conversion about replace...

Page 13: ...y Yes Physical Total of UPS Receptacles 7 Maximum Dimensions 2U Rack 2 Weight lbs 122 5 Battery Sealed Maintenance Free Lead Acid Battery 7AHx8 Typical Recharge Time 8 Hours Warning Diagnostics Indica...

Page 14: ...s providing battery power to the Battery backup outlets Off Off On Set Rapid Beeps Utility Failure The UPS is providing battery power Rapid beeps indicate the battery will run out of charge within a f...

Page 15: ...rings or other metal objects 2 Only use tools with insulated handles 3 Do not lay tools or metal parts on top of battery or any terminals 4 Wear rubber gloves and boots 5 Determine if the battery is i...

Page 16: ...f the Product and therefore entitled coverage under the Limited Warranty Registration is not required for Limited Warranty coverage but note if you do not complete a registration card you will be requ...

Page 17: ...Product if defective within a reasonable time Legacy will refund to you the full purchase price you paid for the Product purchase receipt showing price paid is required CONDITIONS TO THE LIMITED WARR...

Page 18: ...e States or Provinces do not allow the exclusion or limitation of incidental or consequential damages so the above limitation may not apply to you DO NOT USE FOR HIGH RISK ACTIVITIES Legacy does not s...

Page 19: ...ase the separation between the equipment and receiver 3 Connect the equipment into an outlet on a circuit different from that to which the receiver is connected 4 Consult the dealer or an experienced...

Reviews: