2.1 INDICATORS
2.1.1 GENERAL CONDITION INDICATORS
Condition indicators show at all times the operating condition of the equipment or system.
(a) EMG: "EMERGENCY"
Active (on) when the equipment is in an emergency operation condition (voice alarm),
either by manual or automatic activation from the ECI of any voice alarm zone. When in the
emergency condition a warning voice is being issued, whether through emergency microphone or
through recorded evacuation message, the indicator will light up intermittently. Red color.
Simultaneously to the indicator lighting, a continuous audible warning will sound. This
warning can be silenced with the "ACK" control, or automatically when the emergency microphone
is used.
(b) RMT CTRL: "REMOTE CONTROL"
Active (on) when the equipment is remotely controlled from the system controller, or from another
VAP 1 with higher priority. This indicator is deactivated automatically when it starts to operate from
the VAP 1. Amber color.
(c) POWER: "POWER"
Active (on) when the equipment is powered from any possible power supply. Green color.
(d) FLT: "FAULT"
Active (on) when the equipment is in fault condition. This indicator is activated automatically
after detecting a fault of any of the monitored functions. Amber color.
Simultaneously to the indicator lighting, an audible intermittent warning will sound. This
notice can be silenced with the "ACK" control or automatically control when the emergency
microphone is used.
2.1.2 SUPERVISED FUNCTIONS INDICATORS
Supervised function indicators show the faults that affect the general system functions.
These indicators are grouped under the general indicator "FAULT".