22
BCB Input Port
The default function of J6 and J7 are the ports of BCB. The port diagram is shown in Figure2-14,
and description is shown in Table 2-9.
B
C
B
_
D
R
V
B
C
B
_
C
O
N
T
J6-1
J6-2
+24V
+24V
G
N
D
G
N
D
B
C
B
_
O
N
L
J7
+24V
G
N
D
Figure 2-14
BCB Port
Table 2-9
Description of BCB port
Port
Name
Function
J6-1-1
BCB_DRIV
BCB contact drive, pr24V voltage
,
20mA
drive signal
J6-1-2
GND_DRY
Power ground for +24V
J6-2-1
BCB_Status
BCB contact status, connect with the normally open
signal of BCB
J6-2-2
GND_DRY
Power ground for +24V
J7-1
BCB_Online
BCB on-line input (normally open), BCB is on-line
when the signal is connecting with J7-2
J7-2
GND_DRY
Power ground for +24V
Battery Warning Output Dry Contact Interface
The default function of J8 is the output dry contact interface, which presents the battery warnings
of low or excessive voltage, when the battery voltage is lower than set value, an auxiliary dry contact
signal will be activated via the isolation of a relay. The interface diagram is shown in Figure2-15,
and description is shown in Table 2-10.
Figure 2-15
Battery warning dry contact interface diagram
J8
B
A
T
_L
O
W
_N
C
B
A
T
_L
O
W
_N
O
G
N
D