Press Menu
Select Key
Press Digit
Select Key
Press Value Select
Key
SEtuP
Meter Setup
(continued)
00_0
0
Control inputs 1 & 2
(continued)
8
1 = Function Reset 2 = Display Blank
9
1 = Hold
2 = Display Blank
A
1 = Peak or Valley 2 = Display Blank
B
1 = Tare
2 = Display Blank
C
1 = Valley Display 2 = Peak Display
D
1 = Tare
2 = Tare Reset
Both inputs 1 and 2 set to 1 for selections
2
,
4
,
A
,
C
= Function Reset (fast, 20 msec).
Both inputs 1 and 2 set to 1 for selections
0
,
1
,
3
,
5
,
8
,
9
,
B
,
D
= Meter Reset (slow, 2
sec, same as removing & reapplying
power).
ConFG
Meter
Configuration
0
0000
Operation as a
rate of change meter.
Extended meter only.
0
Not rate of change
3
Rate x 10
1
Rate x 0.1
5
Rate x 1000
2
Rate x 1
6
Rate x 10000
0
0
000
Operation of front
panel
PEAK
button
and rear connector for
Peak or Valley Display
0
Peak Display. Also selects “Peak” in
“Peak or Valley” at connector above.
1
Valley Display. Also selects “Valley” in
“Peak or Valley” at connector above.
2
Peak (1st push), Valley (2nd push)
3
Front panel Tare
00
0
00
Auto-tare selection
0
No auto-tare
1
Auto-tare
000
00
RTD or Ohms wiring
RTD
Ohms
00
3 or 4 wire
3 or 4 wire
01
Not allowed
Custom curve
10
2-wire read
2-wire read
11
2-wire short
2-wire short
FiLtr
Filtering
0
0000
Alarm filtering
0
Unfiltered output
1
Filtered output
0
0
000
Peak & Valley filtering
0
Unfiltered Peak & Valley
1
Filtered Peak & Valley
00
0
00
Display filtering
0
Display 16-reading batch average every
17 readings. Updates display 3.5 times/
sec at 60 Hz, 3.0 times/sec at 50 Hz.
1
Display per input signal filter setting
below
000
0
0
Adaptive filter
threshold for all filters
0
Low adaptive filter threshold level
1
High adaptive filter threshold level