- 6 -
ELECTRICAL CONNECTIONS
TERMINALS LEGEND
1
+SUPPLY (12/24 VDC)
115/230 VAC optional version:
+OUTPUT (24 VDC)
15
OUTPUT No. 5: TOLERANCE
otherwise:
+ANALOG OUTPUT (0÷10 V)
2
-SUPPLY (12/24 VDC)
RS232, RS485: SHIELD, GND
E/EC OPTION: GND
115/230 VAC optional version:
-OUTPUT (24 VDC)
RS232, RS485: SHIELD, GND
E/EC OPTION: GND
16
E/EC OPTION
otherwise:
-ANALOG OUTPUT COMMON
3 RS232: TXD
17 RS485: -
4 RS232: RXD
18 RS485: +
5 OUTPUT No. 1: PRESET
19 -LOAD CELL EXCITATION (-Exc)
LOAD CELL SHIELD
6 OUTPUT No. 2: SET
20 +LOAD CELL EXCITATION (+Exc)
7 OUTPUT No. 3: CYCLE END
21 +LOAD CELL REF/SENSE
8 OUTPUT No. 4: ALARM
22 -LOAD CELL REF/SENSE
9 OUTPUT COMMON
23 -LOAD CELL SIGNAL (-Sig)
10 INPUT No. 1: START
(+VDC min 5 V max 24 V)
24 +LOAD CELL SIGNAL (+Sig)
11 INPUT No. 2: STOP
(+VDC min 5 V max 24 V)
L PHASE
(115/230 VAC optional version)
12 INPUT COMMON (-VDC 0 V)
N NEUTRAL
(115/230 VAC optional version)
13
GROUND
(115/230 VAC optional version)
14
INPUT No. 3: selectable
(+VDC min 5 V max 24 V)
otherwise:
+ANALOG OUTPUT (0÷20 o 4÷20 mA)
BASIC INFORMATION
-
It is recommended that the power supply negative pole be grounded.
-
It is possible to supply up to eight 350 ohm load cells or sixteen 700 ohm load cells.
-
For 4-wire load cells, make a jumper between EX- and REF- and between EX+ and REF+.
-
Connect terminal “– SUPPLY” to the RS485 common of the connected instruments in the event
that these receive alternating current input or that they have an optically isolated RS485.
-
In case of an RS485 network with several devices it is recommended to activate the 120 ohm
termination resistance on the two devices located at the ends of the network, as described in the
paragraph
RS485 SERIAL CONNECTION.
-
Option
E/EC
: selects the first 12 formulas.