PLMNL0232 REV. H Effective Date: 01/14/19
53
FiberCUT
®
2D Operation Manual
7 Troubleshooting
SYMPTOM
CAUSE
REMEDY
HSU Fault:
1: Tip Open
There is no connection between the HSU
and tip assembly during calibration.
Verify that the tip assembly and
internal sense cables are properly
installed and then recalibrate.
HSU Fault:
2: Tip Shorted
The tip is not fully insulated from ground
and the body of the cutting head during
calibration.
Remove any debris that may be
causing a short and then
recalibrate.
HSU Fault:
3: Cable Break
The connection between the HSU and tip
has been broken.
Verify that the tip assembly and tip
are properly installed and then
recalibrate.
HSU Fault:
5: Curve Data Error
There is no curve data in the selected
location or the data failed to load correctly.
Load the curve data again or
select a different curve number.
HSU Fault:
6: Invalid curve
number
The value in the Set HSU Curve Industrial
Ethernet register is outside the allowed
range
(1-31).
Enter a valid number or 0 to idle
the input.
HSU Fault:
7: Failed to set
curve
The HSU did not respond successfully to a
value change in the Set HSU Curve
Industrial Ethernet register.
Attempt to set the curve again by
setting the value to 0 and then to
the new curve number.
Verify the head and HSU are
properly connected.
Lens Fault
The lens was out of the commanded
position for an excessive amount of time.
Activate the
Reset
bit or button to
re-establish the zero position of
the motor.
The motor may have stalled or lost its zero
position.
Verify the motor is connected.
Purge Fault
The purge pressure is too low or too high.
Verify the purge gas is turned on
and properly regulated.
Expand the allowable range by
lowering or raising limits.
Temperature Fault
The temperature of one or more sensors
has exceeded the limit.
Allow the component to cool.
Consider raising the temperature
limit if it is safe.
A cover glass drawer has been removed.
Verify the drawers are fully
inserted and the doors are latched
securely.
A temperature sensor is disconnected.
Check the internal cable
connections.
Position Error
The Move Lens command could not be
completed because the value in the Set
Position Industrial Ethernet register is
above the Maximum Position or a Lens
Fault exists.
Clear the
Move Lens
bit. Activate
the
Reset
bit if necessary. Enter a
value that is less than or equal to
the Maximum Position and set the
Move Lens
bit again.
Continuity between
the upper plate and
tip
Tip Retainer Assembly assembled
incorrectly or damaged
Repair or replace the tip retainer
assembly according to
Purge Fault
Incorrect zero pressure point
Activate the
Zero Pressure
bit