Instruction Manual 

Do not attempt installation until you are familiar with all warnings, precautions, and procedures outlined within 
this instruction sheet. 

WARNING: 

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE 
REFERENCE. CRITICAL SAFETY INSTRUCTIONS: 

To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected, and
maintained by a qualified electrician only, in accordance with all applicable electrical codes.

To avoid electric shock: 

Be certain electrical power is OFF before and during installation and maintenance.

Luminaire must be supplied by a wiring system with an equipment grounding conductor.

To avoid burning hands: 

Make sure lens and housing are cool when performing maintenance.

To avoid explosion: 

Make sure the supply voltage is the same as the luminaire voltage.

Do not install where the marked operating temperatures exceed the ignition temperature of the
hazardous atmosphere.

Do not operate in ambient temperatures above those indicated on the luminaire nameplate.

Use proper supply wiring as specified on the luminaire nameplate.

All gasket seals must be clean.

Before opening, electrical power to the luminaire must be turned off. Keep tightly closed when in
operation.

Use only UL listed components suitable for Class I Division 1, Groups C & D and Class II Division 1,
Groups F & G installation.

All threaded connections must engage five full threads.

Refer to the luminaire nameplate for specific 
classification information, maximum ambient 
temperature suitability, and corresponding 
operating temperature (TCode). 

MOUNTING & WIRING 

1.

Mount the enclosure to surface in a location
that can support the load. Use single bolt to
provide rotation when mounting.

2.

Loosen the two set screws on the bracket to
adjust vertical position as necessary.

WIRING 

1.

Remove the front cover module by
loosening the single set screw and rotating
counter-clockwise.

2.

Pull field wiring into module. This light
connects to the corresponding wires on the
main unit.

3.

Close all unused conduit entries with
conduit plugs. To ensure water-tightness,
lubricate conduit plugs with lubricant before
installing, and secure wrench-tight with at
least five (5) full threads engaged (42-52 ft.-
lb. for 3/4” plugs, and 58-68 ft.-lb. for 1”
plugs).

4.

Connect supply wires to luminaire wire
leads (or terminal blocks) using methods
that comply with all applicable codes.
Tighten all electrical connections.

5.

Close cover module, making sure that all
wires are safely inside driver. Tighten
captive closing screw.

6.

Turn power on and aim light.

Voltage:

 12V DC 

Larson Electronics, LLC

 

 Phone: (800) 369-6671 

Fax: (903) 498-3364 

www.larsonelectronics.com 

5

Summary of Contents for EXP-EMG-EXT-LE6-4L

Page 1: ...EXP EMG EXT LE6 4L Explosion Proof Bug Eye Emergency LED Fixture Instruction Manual...

Page 2: ...of your new emergency fixture Following these instructions will insure many years of safe and dependable service Table of Contents I Installation Operation 2 I I Installation 2 2 I II Trouble Shooting...

Page 3: ...e not in use Both battery legs must be connected together This prevents the battery from draining during storage and transit DO NOT CONNECT HIGH VOLTAGE TO BATTERY LEGS II Operation 1 Apply AC power t...

Page 4: ...eck that they battery is properly connected If the problem persists replace the battery 2 Problem Emergency lights are dim The battery might not be fully charged Allow battery to recharge for 24 hours...

Page 5: ...d installation Disconnect AC power before servicing and installation DO NOT use this electrical equipment for anything other than its intended use The use of accessory equipment is not recommended by...

Page 6: ...urned off Keep tightly closed when in operation Use only UL listed components suitable for Class I Division 1 Groups C D and Class II Division 1 Groups F G installation All threaded connections must e...

Page 7: ...To clean wipe the lens with a clean damp cloth If this is not sufficient use a mild soap or a liquid cleaner such as Collinite NCF or Duco 7 Do not use an abrasive strong alkaline or acid cleaner Dama...

Page 8: ...se fittings The sealing compound is mixed with water at the rate of three 3 parts of sealing compound to one 1 part of water by volume See chart to determine the amount of compound required for a spec...

Page 9: ...277VAC HOT BLACK 120VAC HOT WHITE COMMON GREEN GROUND YELLOW REMOTE HEAD POSITIVE PURPLE REMOTE HEAD NEGATIVE BUG EYE FIXTURE REMOTE HEAD BATTERY 1 BATTERY 2 JUNCTION BOX CONNECT CONNECT SEE WIRE LAB...