background image

INSTALLATION, OPERATION & MAINTENANCE DATA SHEET 

TYPE "EYS" HORIZONTAL / VERTICAL SEALING FITTING 

SUITABLE FOR CLASS I, DIV. 1 & 2, GROUPS A, B, C & D 

AND CLASS II, DIV. 1 & 2, GROUPS E, F & G HAZARDOUS LOCATIONS. 

Sealing fittings are installed in conduit runs to minimize the passage of gases, vapors, or flames from one portion of the electrical

installation to another through the conduit, as well as to prevent precompression or "pressure-piling" of vapors or gases in conduit systems. 

NOTE:  

Seals should be made only by experienced, careful persons in strict compliance with these instructions.  Even slight variations can 

cause serious field problems.  Read directions completely. 

DIRECTIONS FOR INSTALLATION

      Using the drawings and chart at the right as a guide, install the sealing 

fitting into the conduit system.  Refer to the National Electrical Code, 

Articles 501-5 and 502-5 for the regulations covering your specific 

application.

Pull the conductors (wires) through the conduit system. 

Using Packing Fiber, build a dam at each conduit hub (except upper hubs 

in vertical seals.)  Use a wooden stick to force the wires apart, and pack 

the fiber tightly around all wires.  The dam must be tight and strong 

enough to keep the liquid sealing compound from leaking out before it 

sets up.  The completed dam should be even with the conduit stop.

Use

 the included 

Sealing Compound with these fittings.  The sealing 

compound is mixed with water at the rate of three (3) parts of sealing 

compound to one (1) part of water by volume.  See chart to determine 

the amount of compound required for a specific fitting.  Use a clean 

mixing vessel for each batch.  Sprinkle the sealing compound into the 

water while stirring, until a thick paste is formed.  Continue mixing for 

AT 

LEAST THREE (3) MINUTES.

  The proper consistency is just fluid 

enough to pour 

SLOWLY

 

, like thick gravy, from an inverted container, 

NOT WATERY.

  Do not mix more material than can be poured in 15 

minutes.  Discard any material that becomes too stiff to use.  Never 

attempt to restore workability by stirring in more water. 

After the compound is mixed, slowly pour it into the sealing fitting to the 

required level.  Make sure that the wires are well separated, so the 

compound completely surrounds them.  Pour slowly to avoid trapping air 

bubbles in the compound.  Immediately wipe any spilled compound from 

conduits and threads, and close the fitting with the close-up plug.  Make 

sure the plugs are tight. 

 Initial set of the sealing compound will occur within thirty (30) minutes.  

However, the compound requires a minimum of 8 hours above 32° F to 

develop sufficient strength to withstand explosion pressures. 

*

NOTE:  

These fittings are approved for use 

only

 with Killark "SC" Sealing Compound.

CONDUIT SIZE 

MIN. POUR 

DEPTH 

APPROX. AMOUNT MIXED 

COMPOUND REQ'D. (OZ.) 

½" 

1.0 

"

1.5 

¾"  

¾"  

2.5 

1"  

1"  

5.5 

1¼"  

1¼"  

7.5 

1½"  

1½"  

10.5 

2"  

2"  

EXP-EMG-EXT-LE6-4L 

Larson Electronics, LLC

 

 Phone: (800) 369-6671 

Fax: (903) 498-3364 

www.larsonelectronics.com 

7

 

Summary of Contents for EXP-EMG-EXT-LE6-4L

Page 1: ...EXP EMG EXT LE6 4L Explosion Proof Bug Eye Emergency LED Fixture Instruction Manual...

Page 2: ...of your new emergency fixture Following these instructions will insure many years of safe and dependable service Table of Contents I Installation Operation 2 I I Installation 2 2 I II Trouble Shooting...

Page 3: ...e not in use Both battery legs must be connected together This prevents the battery from draining during storage and transit DO NOT CONNECT HIGH VOLTAGE TO BATTERY LEGS II Operation 1 Apply AC power t...

Page 4: ...eck that they battery is properly connected If the problem persists replace the battery 2 Problem Emergency lights are dim The battery might not be fully charged Allow battery to recharge for 24 hours...

Page 5: ...d installation Disconnect AC power before servicing and installation DO NOT use this electrical equipment for anything other than its intended use The use of accessory equipment is not recommended by...

Page 6: ...urned off Keep tightly closed when in operation Use only UL listed components suitable for Class I Division 1 Groups C D and Class II Division 1 Groups F G installation All threaded connections must e...

Page 7: ...To clean wipe the lens with a clean damp cloth If this is not sufficient use a mild soap or a liquid cleaner such as Collinite NCF or Duco 7 Do not use an abrasive strong alkaline or acid cleaner Dama...

Page 8: ...se fittings The sealing compound is mixed with water at the rate of three 3 parts of sealing compound to one 1 part of water by volume See chart to determine the amount of compound required for a spec...

Page 9: ...277VAC HOT BLACK 120VAC HOT WHITE COMMON GREEN GROUND YELLOW REMOTE HEAD POSITIVE PURPLE REMOTE HEAD NEGATIVE BUG EYE FIXTURE REMOTE HEAD BATTERY 1 BATTERY 2 JUNCTION BOX CONNECT CONNECT SEE WIRE LAB...

Reviews: