11
3 Installation and Commissioning
3
Installation and Commissioning
For installing the device, check the instruction and installation manuals as well as valid norms,
standards and directives for the application (see also chapter
WARNING!
Connect the device only to other components or devices which are suitable for this safety ap-
plication.
WARNING!
The Appendix see chapter
7.2 Hints and requirements for installation, commissioning, opera-
shall be considered properly. Check the installation requirements of IP40
or IP54 in the open air (EN 60529).
WARNING!
For the power supply of the flame detector and for potential separation of the flame detector
contact use the FN20 power supply. Instead of FN20 a safety power supply must be used to
generate the power supply of the flame detector (e.g. According to EN 61558-2-6 or
EN 60950-1).
WARNING!
Use a floating contact which is feeded by the flame detector's 24 V supply for the remote
switching of the F200K2's range. Or use a SELV or PELV power supply according to EN
60730-1 or EN 60950-1 (i.e. a safety power supply).
WARNING!
The current loop for remote indication of the flame intensity must be connected to devices
which have a safe isolation of the measuring circuit to dangerous active parts in accordance
with EN 61140 ( e.g. by double or reinforced isolation in accordance with EN 61010-1). This
can be, for example, passive instruments or isolating transformers with galvanic 3-way isola-
tion.
WARNING!
Models F200K…IR… without line frequency rejection shall be mounted such that they can
only be removed from the mounting fixture by use of a special tool.
NOTICE
The cables are designed for a special temperature range. Do not open the devices in temper-
atures below -20 °C.
For the commissioning of the F200K please refer to the manual (Chapter 7).
Summary of Contents for F200K2 IR-1
Page 1: ...www lamtec de Sensors and Systems for Combustion Engineering Safety Manual F200K...
Page 2: ......
Page 18: ...17 7 Appendix 7 Appendix 7 1 T V Confirmation...
Page 19: ...18 7 Appendix...
Page 21: ...20 8 EU Declaration of Conformity 8 EU Declaration of Conformity...
Page 22: ...21 8 EU Declaration of Conformity...