34
11
Appendix
Connection cable for ionisation electrode
< 10 m/32,8 ft
Connection cable for auxiliary power
<
3
m/9.8
ft
UV input
Sensor voltage supply (Auxiliary power)
> 200 VAC- lead mains potential
Permitted external input voltage to
X16/1 for connection of a switch contact
230
VAC
50/60
Hz
Input current in the ON state
I
min
= 100
μ
A
Mode
Intermittent operation
Burner restart every
≤
24
h
necessary
Connection cable
<
10
m/32.8
ft
LDR input
Sensor voltage supply (Auxiliary power)
≤
42
V - lead mains potential
Detectable sensor resistance range
220
Ω
...
220
K
Ω
Flame ON
Sensor current
≤
100
μ
A
Mode
Intermittent operation
Burner restart
≤
24
h
necessary
Short-circuit detection
Yes
Connection cable
<
10
m/32.8
ft
Input parameters
Output parameters
Output contact status signal
Contact
Not safety-oriented, floating contact
Contact type
NO, in the event of a malfunction, the contact is closed.
Protection class
SKII, base isolation for the flame signal
Permissible switching voltage
1
230
VAC
cos
φ
≥
0.3
Contact fusing (internal)
1
AT
Specified external contact fusing
1
0.5
AT
Flame signal output contact
Contact
Safety-oriented, floating contact
Contact type
NO, for "flame ON", the contact is closed
Protection class
SKII, base isolation for the status signal
Permissible switching voltage
1
≤
230
VAC
≤
48
VDC
Permissible switching current
1
Max. 0.5
A
cos
φ
0,4
Min.
10
mA
provide external spark suppression for inductive loads,
do not switch capacitive loads.
Contact fuse (soldered)
0.5
AT
Safety time (FFDT) Response time in the event
of the flame going out
t
V
Off
configurable to 1
s
or
3
s
(standard
1
s)
by
using
the
DIP
switch
Switch-on time
t
V
On
≤
1
s
Analogue output (current loop)
- Leads mains potential not safety oriented
Current
0/4
…
20
mA