Commissioning
NOTICE
Shielding/extension of connecting cables
Warning to avoid damage to property
Apply shielded cables directly (without any intermediate terminals if at all possible).
If intermediate terminals are necessary, take the shortest route to applying the shielding
to the terminal.
Avoid long connecting wires without shielding.
Use a separate, shielded extension cable to implement an extension on site.
NOTICE
High electromagnetic interference
Excessive electromagnetic interference can lead to sporadic problems with flame detection
and even prevent it.
In individual cases, a connection between device ground and functional earth ground
(FPE) can remedy this.
NOTICE
EMC emission testing
It was ascertained during the type test that the device meets the EMC emissions require-
ments. A separate EMC emissions test is not necessary after installation.
5.2
Setup
The following sections provide information on:
•
What prerequisites have to be met to install the product properly
•
How you have to position the product
•
How you have to secure the product
5.2.1
Electrical Connection
You can find connection and terminal connection diagrams in the appendix,
NOTICE
A conversion to the respective mains frequency is not necessary.
The device functions in the frequency range specified in chapter