334
EN
cod. 3541V620 - Rev. 00 - 05/2021
ALHENA TECH H
A06
No flame after the ignition phase
Ionization electrode fault
Check the position of the ionization electrode, free
it from any encrustations and do the Calibration
procedure [AUTO SETUP]. Replace the electrode
if necessary.
Flame unstable
Check the burner
air/fume ducts obstructed
Remove the obstruction from the flue, fume extrac-
tion ducts, air inlet and terminals
Trap blocked
Check the trap and clean it if necessary
Wrong calibration
Do the Calibration procedure [AUTO SETUP].
Insufficient gas supply pressure
Check the gas supply pressure
F15 - A07
High fume temperature
The fume probe detects an
excessive temperature
Check the exchanger
Check the flue gas probe
Check the flue material parameter
A08
Overtemperature protection
intervention
Sensor not correctly positioned
on flow pipe or damaged
Check the correct positioning and operation of the
heating sensor and replace it if necessary
No water circulation in the system Check the circulating pump
Air in the system
Vent the system
A09
Exchanger protection interven-
tion
No water circulation in the system Check the circulating pump and heating system
Poor circulation and anomalous
flow probe temperature increase
Vent the system
blocked exchanger
check the exchanger and system
F09
Overtemperature protection
intervention
Flow sensor damaged
Check correct positioning and operation of the flow
sensor and replace it if necessary
No water circulation in the system Check the circulating pump and heating system
Air in the system
Vent the system
F10
Flow sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
A11
Gas valve connection
Damaged electrical connection
between the control unit and gas
valve
check the wiring, or replace the valve
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F13
Fume probe fault
Probe damaged
Check the wiring or replace the fume probe
Wiring shorted
Wiring disconnected
A14
Fume extraction duct safety
device intervention
Fault A07 generated 3 times in
the last 24 hours
See fault A07
F34
Supply voltage under 180V
Electric mains trouble
Check the electrical system
F35
Wrong supply frequency
Electric mains trouble
Check the electrical system
A23-A24-A26-F20
F21-F40-F47-F51
Pressure sensor fault
Wrongly configured parameter
Check if the parameter
b04
is correctly configured
System pressure problems
(transducer)
System pressure value outside set limits (transdu-
cer)
b06
set to 3
F37
Incorrect system water pressure
Pressure too low
Fill the system
Water pressure switch damaged
or disconnected
Check the water pressure switch
F39
External probe fault
Probe damaged or wiring shorted Check the wiring or replace the sensor
Probe disconnected after activa-
ting the sliding temperature
Reconnect the external probe or disable the sliding
temperature
F19
Card parameter fault
Wrong card parameter setting
Check and if necessary modify parameter b15 to 3
Fault code
Fault
Possible cause
Cure
Summary of Contents for ALHENA TECH 28 H
Page 45: ...45 IT cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6 ...
Page 103: ...103 ES cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6 ...
Page 160: ...160 RO cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6 ...
Page 217: ...217 PL cod 3541V620 Rev 00 05 2021 ALHENA TECH H wygląd 48 wygląd 49 wygląd 50 5 6 6 ...
Page 275: ...275 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H İȚț 48 İȚț 49 İȚț 50 5 6 6 ...
Page 330: ...330 EN cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6 ...
Page 343: ......