Version 3.11
| HPI Combi Flow User Guide |
49
www.lafert.com
9.5.2. Parameter Group 7 – Motor Control
Par.
Function
Setting Range
Default
Notes
P7-01
Motor Stator Resistance
0.000 – 65.535
Motor
Rating
Dependent
Motor data, measured or calculated during
the autotune.
P7-06 is used only for PM motors.
P7-03
Motor Stator Inductance (d)
0.0000 – 1.0000
P7-04
Magnetising Current (id)
Drive Dependent
P7-05
Motor Leakage Coefficient (Sigma)
0.000 – 0.250
P7-06
Motor Q Axis Inuctance (Lsq)
0.0000 – 1.0000
P7-09
Over Voltage Current Limit
0.0 – 100.0%
5.0%
P7-10
Load Inertia Constant
0 - 600
10
P7-11
Pulse Width Minimum Limit
0 - 500
P7-12
V/F Mode Magnetising Delay Time
0 – 5000ms
Motor Rating
Dependent
Sets the motor alignment time in PM modes.
P7-14
Low Frequency Torque Boost
0.0 – 100.0%
Motor Rating
Dependent
For PM Motors, applies a torque boost current
at low frequency, % x P1-08.
P7-15
Torque Boost Frequency Limit
0.0 – 50.0%
Motor Rating
Dependent
For PM motors, determines the frequency, % x
P1-09 when the boost current is removed.
P7-18
Over Modulation
0
Disable
0
1
Enable
2
Auto
P7-19
BLDC Light Load Optimization
0
Disable
1
1
Enable
P7-20
Modulation Mode
0
3-Phase Modulation
1
1
2-Phase Modulation
9.6. Parameter Group 8 – Application Function Specific Parameters
Par.
Name
Minimum
Maximum
Default
Units
P8-01
Pump Stir Interval Duration
0
60000
0
Minutes
This parameter can be used to set a pre-defined period of inactivity, whereby if the drive remains in standby mode for a period of time
exceeding the limit, stir function is activated, and the drive will operate at preset speed 7 (P2-07) for the time set in P8-02. This allows
the pump to stir, preventing sediment from settling and avoiding a blockage.
P8-02
Pump Stir Activation Time
1
6000
10
Seconds
Set the time period that the stir function will be active once triggered (excludes time for deceleration to stop).
P8-03
Pump Clean Function Select
0
3
-
-
This parameter configures the drive conditions that will cause activation of the automatic pump clean function. When activated, the
pump clean will operate the pump at preset speed 5 (P2-05) for the time period set in P8-04, followed by Preset Speed 6 (P2-06)
(Providing P2-06 <> 0) for the time set in P8-04, before resuming normal operation. During the cleaning cycle, the ramp time set in P8-
05 is used for both acceleration and deceleration, and overrides P1-03 and P1-04.
Where possible, P2-05 and P2-06 may be set to negative values, to allow the pump to be reversed. For best results, it is recommended
to use as high a speed as possible, and to adjust P8-05 to allow a short acceleration time whilst avoiding over current trips.
0 : Disabled.
1 : Active on start-up only.
The pump cleaning function operates every time the pump is started.
2 : Active on start-up and high current detection.
The pump cleaning function operates every time the pump is started,
and also in the event that the drive detects a possible pump blockage during normal operation. This requires the Motor Current Profile
Monitoring function to be active and commissioned for correct operation, see parameter P8-06.
3 : Active on high current detection only.
The pump cleaning function operates only when a possible pump blockage is
detected during normal operation. This requires the Motor Current Profile Monitoring function to be active and commissioned for
correct operation, see parameter P8-06.
NOTE
The pump clean function can also be activated by digital input configured in group 9 parameters.
P8-04
Pump Clean Time
0
600
0
Seconds
Sets the time period for the operation of the pump cleaning cycle. When bi-directional pump cleaning is selected, the time interval is
used twice, once in each direction.
P8-05
Pump Clean Function Ramp Time
0
6000
30
Seconds
Independent ramp rate used only for the pump automatic cleaning function (see P8-03) when the motor is Accelerated as part of the
cleaning cycle.
9
Extended P
arameters