Par.
Parameter Name
Units
P0-40
Motor Current Log (256ms)
Amps
Diagnostic log for Motor Current. Values logged every 256ms with 8 samples total. Logging suspended on drive trip.
NOTE
The above parameters (P0-36 to P0-40) are used to store the history of various measured levels within the drive at various regular time
intervals prior to a trip. The values are frozen when a fault occurs and can be used for diagnostic purposes.
P0-41
Over Current Fault Counter
-
P0-42
Over Voltage Fault Counter
-
P0-43
Under Voltage Fault Counter
-
P0-44
Heatsink Over Temperature Fault Counter
-
P0-45
Reserved
-
P0-46
Ambient Over Temperature Fault Counter
-
NOTE
These parameters (P0-41 to P0-46) contain a record of how many times certain critical faults have occurred during a drives operating
lifetime. This provides useful diagnostic data.
P0-47
I/O Comms Fault Counter
-
Displays the number of communication errors detected by the I/O processor in messages received from the power stage processor
since the last power up.
P0-48
DSP Comms Fault Counter
-
Displays the number of communication errors detected by the Power Stage processor in messages received from the I/O processor
since the last power up.
P0-49
Modbus RTU / BACnet MSTP Fault Counter
-
This parameter is incremented every time an error occurs on the Modbus RTU communication link. This information can be used for
diagnostic purposes.