11
out1
, menu for parameters of the output 1
Menu is intended for manual setting of PID parameters or for fine tunning of parameters when the controlling is not enough
precise. To enter this menu set
YES
on upper display and confirm.
Display
Meaning
Pb1A
Proportional band of the output 1
, the first set of PID parameters.
Range: 1 to 2499 °C.
It1A
Integral value
of the output 1
, the first set of PID parameters.
Range:
oFF
, 0.1 to 99.9 minutes.
dE1A
Derivative value
of the output 1,
the first set of PID parameters.
Range:
oFF
, 0.01 to 9.99 minutes.
Pb1b
Proportional band
, the second set of PID parameters.
Range: 1 to 2499 °C.
It1b
Integral value
, the second set of PID parameters.
Range:
oFF
, 0.1 to 99.9 minutes.
dE1b
Derivative value,
the second set of PID parameters.
Range:
oFF
, 0.01 to 9.99 minutes.
hYS1
Hysteresis of the output 1
, this single parameter is set only for ON/OFF control.
Range: 1 to 249 °C.
The description of PID parameters is found on page
16
.
out2
, menu for parameters of the output 2
In menu the control parameters of the output 2 (
ot2
=
CL
or
ot2
=
CL2
) are shown or the limits of signal output (
ot2
=
SGPr
or
ot2
=
SGdE
). To enter menu set
YES
on upper display and confirm.
Display
Meaning
Pb2A
Proportional band of the output 2.
Range: 1 to 2499 °C.
It2A
Integral value
of the output 2.
Range:
oFF
, 0.1 to 99.9 minutes.
dE2A
Derivative value
of the output 2.
Range:
oFF
, 0.01 to 9.99 minutes.
hYS2
Hysteresis of the output 2
, this single parameter is set only for ON/OFF control.
Range: 1 to 249 °C.
o2Lo
Low limit of signalling
. Output is activated when process value is
lower
than the set signalling limit.
Range:
•
-499 to
o2hI
°C for
ot2
=
SGPr
.
•
-999 to 0 °C for
ot2
=
SGdE
.
o2hI
High limit of signalling
. Output is activated when process value is
higher
than the set signalling limit.
Range:
•
o2Lo
to 2499 °C for
ot2
=
SGPr
.
•
0 to 999 °C for
ot2
=
SGdE
.
out3
, menu for setting of alarm limits
The menu is shown when the output 3 is set as the alarm one (
ot3
=
ALPr
or
ot3
=
ALdE
). In menu you can choose the limits
of alarm.
Display
Meaning
ALLo
Low limit of alarm
. Alarm is activated when process value is
lower
than the set alarm limit.
Range:
•
-499 to
ALhI
°C for
ot3
=
ALPr
.
•
-999 to 0 °C for
ot3
=
ALdE
.
ALhI
High limit of alarm
. Alarm is activated when process value is
higher
than the set alarm limit.
Range:
•
ALLo
to 2499 °C for
ot3
=
ALPr
.
•
0 to 999 °C for
ot3
=
ALdE
.