background image

 

17 

PID controlling 

PID control is selected by setting 

ot1 

 = 

  ht

 . It provides the precise control. For the correct function of the controller, 

however, it is necessary to set properly PID parameters. Autotunning for setting of PID parameters is described on page 9. 
PID parameters have the following meaning: 

 

Pb

 

proportional band

 is set in measured units. It is the band about the set point value in which the controller keeps the 

temperature. 

 

It

 

integral factor

, in minutes. Integral factor compensates the loss of system. A 

low 

integral value causes a 

fast 

integrating action. 

 

dE

 derivative factor

, in minutes. Derivative responses to fast changes and tries to react against them. The 

more

 value is, 

the 

more 

derivative factor reacts. 

If the control output is 2 state (ON/OFF) (relay or SSR), the power is (given in %) transferred to the output with so called pulse 
width modulation. In each time cycle (parameter 

Ct1 

, you will find it in 

configuration level

, menu 

out1

) the control output is 

switched ON once and once OFF. The more the power is necessary, the wider the width of switching is. The output responses 
are illustrated in the third part of the drawing. 

 

Power limit function  

You can improve the quality of control by limiting of the output power.  
 

Process 
value  

Time 

STP value 

Output 
power 

Time 

100 % 

State 

of 

control 
output 

Time 

ON 

OFF 

Time cycle 

Example of pulse width modulation of 

the output: 

 

Time cycle is 10 seconds, the power requested 
is 30%. The output is ON for 3 seconds and 
OFF for 7 seconds. 

 

Time cycle is 10 seconds, the power requested 
is 5%. The output is ON for 0,5 second and 
OFF for  9,5 seconds. 

Important: 

 

The duration of time cycle has the influence on 
the quality of control. The longer the cycle is, 
the less the quality of control is. 

 

If the electromechanical unit (relay, switching 
contactor) is used for the control output, the 
duration of time cycle must be set longer with 
regard to lifetime of switch. 

 

Process 
value 

time 

S PL 

Power 

limit 

function  above 

PLhI

  

Power 

limit 

function    below 

PLLo

   

Example how to use the power limit 

function: 

When rising at set point value the big overshoot occurs. 
One of possible solution is the power limit in the vicinity 
of set point value. The procedure is the following: 

 

Find out the power supplied to the stable system. 

 

Set the switcher 

S PL

 on the value by several 

o

C less 

than set point value. 

 

Set power limit 

PLLo

 to 100%. 

 

Set power limit 

PLhI

 approx. by 10 to 20% higher 

than the power supplied to the stable system. 

 

Summary of Contents for Ht40B

Page 1: ...1 Ht40B 01 03 soft 4 11 rev 1 english version Ht40B PID controller Users manual LAC spol s r o tef nikova 116 664 61 RAJHRAD e mail info lac cz www lac cz...

Page 2: ...t you need for your own work on the controller If you are a new user of the device focus on the following chapters Basic terms here it is explained the key functions displays and so on Basic mode the...

Page 3: ...asing a value of parameter key for switching between automatic and manual operation see page 8 2 2 Information and error messages Information and error messages are indicated only in basic mode see pa...

Page 4: ...t is necessary to set up its parameters properly For better understanding the parameters are sorted out to groups levels and menus Level is superior to menu menu is a part of level menu out1 The struc...

Page 5: ...set for the output on lower display heading oFF is lit and the control output is switched OFF When in cascade controlling there is calculated stp value shown on lower display and heading CSCd blinks W...

Page 6: ...munication line it is used for system Master Slave CSCD remote setting of stp value via communication line it is used for cascade controlling dIF Difference of remote stp value for system Master Slave...

Page 7: ...set no You can view the result in user level 4 1 Controlling of stp value When the controller maintains stp value lower display shows stp value and upper display shows process value Setting of stp va...

Page 8: ...f the control output PID controlling The controller Ht40B can be configured for ON OFF as well as PID controlling and it enables Heating controlling the output 1 Cooling controlling the output 2 Contr...

Page 9: ...Aut CL setting parameters for cooling Parameter Aut you will find in operation level The control output must be set for PID controlling The controller explores the characteristics of system from swit...

Page 10: ...ing of PID parameters oFF turning OFF of autotunning of PID parameters ht starting of autotunning of PID parameters heating CL starting of autotunning of PID parameters cooling L r Selection for setti...

Page 11: ...are shown or the limits of signal output ot2 SGPr or ot2 SGdE To enter menu set YES on upper display and confirm Display Meaning Pb2A Proportional band of the output 2 Range 1 to 2499 C It2A Integral...

Page 12: ...per display set via the arrow keys ConF and confirm If PASS appears on lower display configuration level is secured with the password In this case set the password via the arrow keys and confirm again...

Page 13: ...1 Together with parameter rh 1 you also set the scale of displaying measured values for process input ranges Range 499 to rh 1 rh 1 Together with parameter rL 1 you also set the scale of displaying me...

Page 14: ...alarm defined by the deviation from stp value SP1 Lat3 Setting for alarm latching oFF temporary alarm on permanent alarm SIL3 Setting for alarm silencing at the power up oFF alarm function is active...

Page 15: ...ON OFF controlling o2Lo low limit of signalling for the output 2 o2hI high limit of signalling of the output 2 ALLo low limit of alarm ALhI high limit of alarm StP2 Parameter that is placed on the 2nd...

Page 16: ...broken the control output is turned OFF the alarm output is activated Measuring range of process inputs In configuration level menu InP1 you can define the measuring range of the process inputs with p...

Page 17: ...of the drawing Power limit function You can improve the quality of control by limiting of the output power Process value Time STP value Output power Time 100 State of control output Time ON OFF Time c...

Page 18: ...the absolute value of temperature ot3 ALPr Alarm defined by the deviation from stp value ot3 ALdE Temporary permanent latched alarm Alarm can be temporary LAt3 oFF or permanent LAt3 on Temporary alar...

Page 19: ...stp value Slave controllers can modify this value by difference parameter dIF Multi zone furnace Master controller Slave controller T R T R As MASTER conroller you can use also other controllers INDUS...

Page 20: ...n ON of action unit is too e g in muffle furnace By configuration of 2 controllers as a cascade system you achieve that long lag time will be divided into 2 parts and thus you improve the quality of c...

Page 21: ...ce rtd input 1 Range 350 ohms I1 Measured current current input 1 Range 20mA u1 Measured voltage voltage 1 Range 10V ConF By setting YES and confirming you enter the menu for setting all the parameter...

Page 22: ...vel Sen1 dEC1 CAL1 rL 1 rh 1 CoMM bAud Addr ot1 Ct1 ALGo SPid PLLo S PL PLhI ot2 FKEY SP1L SP1h rAMP rtI P oP P Co P SE Ftr1 SP2 Ct2 SId2 ot3 Lat3 SIL3 SId3 hYS3 rErr dErt StP1 StP2 StP3 StP4 StP5 StP...

Page 23: ...rence in environment of the controller Among the most harmful sources of interference are the following Equipment with inductive load e g electromotors winding of relays and breakers Thyristors and ot...

Page 24: ...nect the unit to a supply power source check the level of supply voltage The controller is intended for use in industrial or in laboratory equipment measuring input InP1 Fuse T 1A 100 240 VAC 50Hz max...

Page 25: ...ated from the ground of the controller For this output it is necessary to fix the wires in the way that in case of loosening the wire from the terminal the insulation would not be reduced between supp...

Page 26: ...sary to fix the wires in the way that in case of loosening the wire from the terminal the insulation would not be reduced between supply voltage and safety voltage 230Vac 5A or 30Vdc 5A 1 2 3 4 5 6 7...

Page 27: ...position of decimal point You will find the description of this parameter on page 16 This parameter is shown only for the process input rL 1 rh 1 parameters for setting of the scale of displaying val...

Page 28: ...00 C r thermocouple R range 0 to 1760 C S thermocouple S range 0 to 1760 C b thermocouple B range 300 to 1820 C C thermocouple C range 0 to 2320 C d thermocouple D range 0 to 2320 C rtd sensor rtd Pt1...

Page 29: ...on this controller with the exception on defects caused by mechanical or electrical wearing out of the outputs This warranty does not also apply to damage resulting from inappropriate transportation...

Page 30: ...ning automatic setting of PID parameters 9 5 Operation level 10 6 Configuration level 12 6 1 Measurement 16 6 2 Controlling the control output 16 6 3 Alarm 18 6 4 System Master Slave 19 6 5 Cascade co...

Reviews: