13
InP1
, input setting
Display
Meaning
SEn1
Setting of input sensor – thermal input.
•
no
… input is not set.
•
J
… thermocouple J, range -200 to 900°C.
•
K
… thermocouple K, range -200 to 1360°C.
•
t
… thermocouple T, range -200 to 400°C.
•
n
… thermocouple N, range -200 to 1300°C.
•
E
… thermocouple E, range -200 to 700°C.
•
r
… thermocouple R, range 0 to 1760°C.
•
S
… thermocouple S, range 0 to 1760°C.
•
b
… thermocouple B, range 300 to 1820°C.
•
C
… thermocouple C, range 0 to 2320°C.
•
d
… thermocouple D, range 0 to 2320°C.
•
rtd
… rtd sensor ( Pt100), range -200 to 800°C.
Setting of input sensor … process input:
•
no
… input is not set.
•
0-20
… 0 – 20 mA, range -499 to 2499 units.
•
4-20
… 4 – 20 mA, range -499 to 2499 units.
•
0-5
… 0 – 5 V, range -499 to 2499 units.
•
1-5
… 1 – 5 V, range -499 to 2499 units.
•
0-10
… 0 – 10 V, range -499 to 2499 units.
dEC1
Setting of decimal point for displaying – thermal input.
•
0
… no decimal point.
•
0.0
… 1 decimal point.
Setting of decimal point for displaying – process input:
•
0
… no decimal point.
•
0.0
… 1 decimal point.
•
0.00
… 2 decimal points.
•
0.000
… 3 decimal points
CAL1
Correction of sensor
. The set value is added to process value.
Range: -999 to 999 °C.
rL 1
Together with parameter
rh 1
you also set
the scale of displaying measured values
for process input ranges.
Range: -499 to
rh 1
.
rh 1
Together with parameter
rL 1
you also set
the scale of displaying measured values
for process input ranges.
Range:
rL 1
to 2499.
Ftr1
You set
filter coefficient for input signal
. The more the filter coefficient is the more the filter smoothes the input signal.
Range:
oFF
, 0.1 to 60.0 seconds.
CoMM
, communication line
Display
Meaning
CoMM
Setting of communication line
:
•
Mod
… the controller is set for communication with PC.
•
SGnL
… the controller transmits information for controlling of SLAVE units.
bAud
Baudrate of communication
,
is in default setting - 9600Bd.
Addr
Address of the equipment
, it is shown when
CoMM
=
Mod
.
out1
, output 1
Display
Meaning
ot1
Function of the control output 1
:
•
oFF
… the output 1 is turned OFF.
•
ht
… the heating control, PID controlling.
•
ht2
… the heating control, ON/OFF controlling
Ct1
Time cycle for switching of the output 1.
Range: 1 to 200 seconds
ALGo
Algorithms of PID controlling:
•
PId
… one set of PID parameters is used.
•
2PId
… both sets of PID parameters are used.
SPId
Limit between PID set 1 and PID set 2.
Range: -499 to 2499 °C.
PLLo
Power limit function for the limiting of output power at low measured values, in %.
Range: 0 to 100 %.