background image

Page 9

3. 

The heaters should be wired exactly as shown in 
the wiring diagram.

IMPORTANT NOTE:

 The pool filter pump 

and heater must be electrically interlocked so the 
heater cannot come on unless the pump is running 

and there is full flow in the filter piping where the 

heater is connected. If the pool filter pump operation 

is intermittent the heater must be shut off prior to 

pump shutdown. See paragraph heading Auxiliary 
Time Clock Wiring below. If the backwash operation 

is manual the heater must be shut off manually during 

backwashing.

Auxiliary Time Clock Wiring:

If a time clock is used to control the filter pump 

operation, a separate switch or relay must be used to 

shut off the heater at least 

15 minutes before

 the filter 

pump is shut off. Wire the switch or relay (often called 

the Fireman Switch) to the terminals shown in the 
wiring diagram as “Field Interlock.”

4.  All field installed electrical safety devices and 

all field installed controllers (valve end switches, 

draft switches, relays, timers) can be connected 
to the heater control to the terminals shown in the 
wiring diagram designated “Field Interlock.”

5. 

Field location of the temperature sensor is 
described in Section 2.8.
Where the heater is installed with a draft fan 

refer to the fan manufacturer's wiring diagram. The 

draft switch should be wired across the field interlock 

terminals in the heater control panel.

2.6  General Piping Instructions

In addition to the bypass valve “A” and outlet 

valve “B” shown in Figure 10, an inlet valve “C” 
should be provided so that the heater can be readily 

isolated for service. All valves should be butterfly or 

ball style, not gate valves. For spas application see 
Section 3.9.

Since heater outlet temperatures can reach  

150°F (66°C) in some cases, copper or CPVC are 
recommended materials for heater connection piping. 
PVC material may be used for the inlet valve and the 
piping upstream of it.

When pipe, fittings, grids or any other element 

of the filter system are made of plastic materials, they 

may be damaged by the momentary "back siphoning" 

of hot water from the heater when the filter pump stops 

running.

The pressure relief valve installed in the tapped 

opening provided in the outlet header (see Figure 9), 

must be piped, but not connected, to a drain or floor 

sink. The drain pipe must be the same size as the 
valve outlet and must pitch downward from the valve. 
Where no special setting of the relief valve is ordered, 
the factory will furnish a 75 psi setting.

The pressure relief valve lever must be tripped 

at least once a year to insure that waterways are clean. 
When manually operating lever, water will discharge 
through the drain line. Precautions must be taken to 
avoid contact with hot water and water damage.

2.7  Heater By-Pass Piping

All models/sizes of this pool heater must be 

installed with bypass piping. Please use Figure 10 as 
your guide to plumb the bypass. For spas see Section 
3.9.

If the distance from the pool heater to the pool 

loop piping is greater than 15' please contact the 
Service Department  for assistance (see back page for 
phone and fax numbers).

All models are supplied with integral pumps, 

These pumps are sized for the pressure drop through 
the heat exchanger, 30' of piping, and through the 
bypass piping as shown in Figure 10.

Any deviations from  the arrangement shown 

may reduce flow, hinder performance, and will void 

the warranty.

2½ inch NPT piping is shown, however, models 

500I-1430I and models 500E-1010E may be installed 
using 2 inch NPT piping.

All models must be installed in the primary/

secondary arrangement shown. The heater loop piping 

must tee into the filter loop piping with the inlet 

and outlet connection spaced a maximum of 4 pipe 
diameters apart (see Figure 10).

To insure that pool inlet water does not exceed 

104°F, the filter pump loop must circulate at the 

minimum flow rates shown in Table 4.

The outlet valve “B” and the bypass valve “A” 

must have a provision for locking the handles in place 
(or removing them) after the temperature rise and inlet 
temperature adjustments have been made.

Figure 9 - Pressure Relief Valve Location

MightyTherm Pool Heater

Summary of Contents for Mighty Therm AP

Page 1: ...pas tenter d allumer d appareils Ne touchez aucun interrupteur Ne pas vous servir des t l phones dansle b timent o vous vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Su...

Page 2: ...or Pool Heaters 7 2 4 Gas Supply and Piping 7 2 5 Electrical Wiring 8 2 6 General Piping Instructions 9 2 7 Heater By Pass Piping 9 2 8 Temperature Sensor Placement and Installation 10 2 9 Automatic C...

Page 3: ...N HEAT EXCHANGER C GLASS LINED COPPER N GLASS LINED CU NI A GLASS LINED COPR REVRSD M GLASS LINED CU NI REVRSD Option Code XX Standard JX CSD 1 HL High low gas pressure switches LC LWCO 100 lockout LW...

Page 4: ...of ANSI standard Z223 1 and any local codes that may be applicable Inadequate combustion air supply may result in incomplete combustion sooting of the heat exchanger and unsafe operation of the heate...

Page 5: ...and must not be connected to any portion of a mechanical draft system under positive pressure The flue outlet must be connected to a clear unobstructed vent of adequate capacity ending above the high...

Page 6: ...ing system are located and the other spaces of the building Turn on any clothes dryer and any appliance not connected to the common venting system Turn on any exhaust fans including range hoods and ba...

Page 7: ...or wall recess Avoid locations where wind deflection off structures might cause downdraft When such wind conditions are possible place the heater at least 3 feet 0 9m from the structures 3 Never insta...

Page 8: ...cifically ordered otherwise 2 The 1825 models are supplied with 3 4 HP pump motors All other models are supplied with 1 2 HP pump motors Consult the National Electrical Code or the Canadian Electrical...

Page 9: ...ilter system are made of plastic materials they may be damaged by the momentary back siphoning of hot water from the heater when the filter pump stops running The pressure relief valve installed in th...

Page 10: ...Controls a Intermittent Ignition Pilots are automatically lit when the operating control calls for heat Systems 4 9 and 11 The unit performs its own safety check and opens the main valves only after...

Page 11: ...e auto reset limit switch is provided as standard equipment on all heaters The temperature sensing bulb of the switch is field installed and should be located in the pool loop piping See Section 2 8 f...

Page 12: ...auses air to be drawn into the heater and the secondary piping an automatic float type air vent should be permanently installed on top of the pump scroll 3 To check the heater firing proceed as follow...

Page 13: ...pen throttle turn down outlet valve B slightly Observe the inlet thermometer for 5 minutes to see where the inlet temperature stabilizes If it remains under 110 F 43 C throttle outlet valve B a little...

Page 14: ...caution is suggested for young children adjusted incrementally to obtain the desired pool operating temperature 7 An adjustable pump time delay relay is mounted in the control panel see Figure 11 Thi...

Page 15: ...30 days 90 days and once every six months thereafter Fouling on the external surfaces of the heat exchanger is caused by incomplete combustion and is a sign of combustion air and or venting problems...

Page 16: ...operating condition and preventing corrosion liming or other problems Proper pool water chemistry includes other values that must be maintained for swimmer safety Refer to your local agency having jur...

Page 17: ...r u s s e r p m o r f y r a s s e c e n s a t s u j d a F Electric gas valve operator is F Disconnect wiring harness at gas valve terminals Check continuity of actuator burned out or shorted coil If o...

Page 18: ...303 10548301 14 Tile Heat Shield Spacer Rear 10548401 10548402 10548403 10548404 15 Saddle Assembly End Tile 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 10533600 2 2 2 2 2...

Page 19: ...Page 19 Figure 17 Parts Identification Mighty Therm Commercial Pool Heating Boiler Page 19 Figure 17 Parts Identi cation ONE PIECE PUMP VOLUTE MightyTherm Pool Heater...

Page 20: ...n Combustible Base Rail 10539000 10539000 10539000 10539000 10539000 10539000 10539000 10539000 10539000 2 2 2 2 2 2 2 2 2 Water System 34 8 Tube Assembly Copper Tubes 10534701 10534702 10534703 10534...

Page 21: ...101 2 2 2 2 2 2 2 2 2 42 Flange Gasket S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 S0063700 2 2 2 2 2 2 2 2 2 43 Header Gasket w Barrier S0095100 S0095100 S0095100 S0095100...

Page 22: ...00 58 Pilot Bracket Burner Weldment 10529502 10529502 10529502 10529502 10529502 10529502 10529502 10529502 10529502 59 Pilot Burner W0035800 W0035800 W0035800 W0035800 W0035800 W0035800 W0035800 W003...

Page 23: ...Control Electronic E2305400 E2305400 E2305400 E2305400 E2305400 E2305400 E2305400 E2305400 E2305400 Single Try 72 Transformer 115V 24V R0021300 R0021300 R0021300 R0021300 R0021300 R0021300 R0021300 R0...

Page 24: ...ssemblies When ordering tiles Assembly number is for all tiles Part numbers shown for the front of unit are the same for the rear tiles Check dimensions of old tile as shown here to confirm part numbe...

Page 25: ...Page 25 Figure 19 Outdoor Parts 1 2 3 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 20 MightyTherm Pool Heater...

Page 26: ...10665907 10665908 10665909 Copper Tube Cast Iron Tubs Outdoor 10 Tube Assembly 20001101 20001102 20001103 20001104 20001105 20001106 20001107 20001108 20001109 Copper Tube Bronze Tubs Outdoor 10 Tube...

Page 27: ...Front End Panel 10657501 10657501 10657501 10657501 10657501 10657501 10657501 10657501 10657501 13 Right Front End Panel 10657502 10657502 10657502 10657502 10657502 10657502 10657502 10657502 10657...

Page 28: ...905 636 0666 www Laars com Litho in U S A Laars Heating Systems 21 10 Document 3006V Laars Heating Systems Company reserves the right to change specifications components features or to discontinue pro...

Reviews: