Page 4
SECTION 2.
Installation
2.1 Pool Heater Placement
The pool heater must be placed to provide
specific clearances on all sides for maintenance and
inspections. There must also be minimum distances
maintained from combustible surfaces. These
clearances also apply to noncombustible materials
because the pool heater requires air circulation for
proper operation.
The pool heater should be mounted on a
level surface. An integral base for an installation
on combustible flooring is provided as standard
equipment on outdoor models. For indoor models,
special base rails part number 10539000 must be used
for combustible flooring.
Do not install a pool heater on carpeting.
Under the national Fuel Gas Code, ANSI Z223.1,
it is permissible to place the pool heater on floors other
than noncombustible when the installation complies
with the American Insurance Code. Figures 2, 3, 4 and
5 show common installation on combustible flooring.
2.2 Installation of Indoor Pool Heaters
Locate the pool heater to provide adequate
clearance for inspection and service on all sides. See
Table 1. For alcove installation, see Figure 6.
Install indoor heaters on a waterproof floor with
an adequate floor drain and a 6" (152mm) minimum
curb on all four sides to protect the building if heater
repairs are required.
The manufacturer will not be
held liable for any water damage in connection with
this pool heater.
2.2.1 Combustion Air Supply
The heater location must provide sufficient air
supply for proper combustion and ventilation of the
surrounding area as outlined in the latest edition of
ANSI standard Z223.1, and any local codes that may
be applicable. Inadequate combustion air supply may
result in incomplete combustion, sooting of the heat
exchanger, and unsafe operation of the heater.
a. Conventional Ventilation
In the United States, the most common of these
requirements specify that pool heater rooms should
be provided with two permanent air supply openings
communicating directly through the wall to outside
air one within 12 inches (305mm) of the ceiling, and
the other within 12 inches (305mm) of the floor. Each
opening should have a minimum free area of one
square inch (6.5 sq. cm) per 4,000 BTU/hr input of
the total input rating of all appliances in the enclosed
area. See Table 2 for recommended air supply for each
Clearance
Indoor
Outdoor
from
in.
mm
in.
mm
Top
30
762
unobstructed
Water Conn. side
12*
305
24
610
Pump side
6*
152
24
610
Front
Alcove*
unobstructed
Rear
8
203
24
610
Vent pipe**
6
152
- - -
Hot water pipes
per code
per code
* Water connection and pump side clearances of 24"
(610mm) and front clearances of 48" (1219mm) will allow
easier service access.
** Using type B vent (refer to Manufacturer's Instructions).
Table 1 - Minimum Heater Clearances
from Adjacent Surfaces
Figure 2 - Typical Heater Installation on Concrete Slab
Figure 3 - Typical Heater Installation on Roof
Using Raised Platform (Wood)
1.5 Certifications
All models are design-certified by CSA for
natural or propane gas and conform to ASME Code
requirement for 160 PSI water pressure.
1.6 Engineering Assistance
Consult the factory or distributor regarding any
questions or problems which arise in the specification,
installation or operation of this pool heater. An
experienced engineering staff is ready to assist in
assuring the proper performance and application.
LAARS Heating Systems