background image

 

LAARS Heating Systems

Page 28

differential/2.

2. Target Max

 - The boiler target maximum is 

the point at which the stages will start to turn off to 

maintain a maximum water temperature.  The Boiler 

Maximum water temperature is set by setting dip 

switch #4: Boiler Maximum 210°F (Off) / 190°F (On).

To ensure that the water temperature is less than 

the Boiler Maximum water temperature the target is 

decreased to allow the stages to cycle off by the Boiler 

Maximum water temperature, Boiler Maximum target 

is set to Boiler Maximum - differential/2.

Auto Differential

  The control automatically 

adjusts differential to prevent short cycling and 

maximize the lifetime of components.

WWSD Operation

  Warm Weather Shutdown - 

WWSD feature is selected via dip switch #3, WWSD 

Inactive (Off) / Active 70°F (On).  WWSD point is 

fixed at 70 deg F.  Control exits WWSD when the 

outdoor temp falls to 65 F.  When there is a call for 

HEAT and the control is in WWSD the HEAT call will 

be ignored.  When there is a call for DHW and the 

control is in WWSD the DHW call will be satisfied.  

WWSD LED turns on when control detects WWSD.

 

Summary of Input Sensors:

1. Outdoor sensor - monitors the outside air 

temperature for outdoor reset mode

2. Boiler outlet sensor -monitors the water 

temperature of the boiler outlet supply

3. System Supply sensor - monitors the water 

temperature of the system supply

The boiler outlet sensor is required at all times.  

If the boiler outlet sensor has any fault then the control 

will flash an error and turns all stages off.  The system 

supply sensor is optional and utilizes  

primary / secondary piping.  If the system supply 

sensor has a fault then the control flashes an error 

message and operates using the boiler outlet sensor 

(system supply = boiler outlet).

6.3  External Boiler Operations

Use the field interlock ( T-T terminals ) that are 

inside control box. 

 

6.4  Sequence of Operation

If a field-supplied pump is properly wired to the 

unit, or if the unit is pump-mounted, the pump will be 

energized. 

Once the water flow switch makes, if all of the 

safety interlocks are closed, the ignition  module will 

energize the blower(s) for a 15-second pre-purge, 

followed by a 40-second period to allow the ignitor to 

heat.

The ignition control energizes the blower. The 

blower pressurizes the air box (which supplies air to 

the burners) and closes the normally-open contact 

on the airflow pressure switch. The blocked vent 

pressure switch senses the pressure in the exhaust 

plenum. This switch opens if the pressure is excessive 

(as an indicator of a blocked vent). When these two 

pressure switches are closed, voltage is sent to the 

PSW terminal on the ignition control, which allows the 

ignition module to proceed with the ignition sequence.

If the airflow proving circuit is not proven, 

ignition module will lock out. 

Section 6.5 

describes 

the result of air flow faults in more detail.

When the ignition control gets the signal at the 

PSW terminal, it will energize its MV terminal, which 

sends power to the stage one (or on/off) main valve.

After a 7-second trial for ignition, the ignitor 

switches to flame sense mode. If a flame is not 

detected, the gas valve will close and the ignition 

module will attempt ignition again (up to two more 

times, for a total of three attempts.) If all three 

attempts fail, the ignition control will lock out.

If flame is sensed, the burner will continue to 

fire as long as there is a call for heat, and none of the 

safety circuit is interrupted.

If there is a call for stage 2 on a 2-stage unit, that 

valve will be energized.

If there is a loss of flame signal during a 

successful firing sequence, the ignition control will 

remove power from the gas valves, and then attempt to 

light up to two more times. If successful, the Mighty 

Therm2 will fire normally. If unsuccessful, the ignition 

control will lock out.

When the call for heat is satisfied, the gas 

valve(s) closes, and the blower starts a 45 second 

post-purge, and the pump starts the post-purge (where 

applicable). 

6.5 Ignition Control Reaction to Air Flow / 

Blocked Vent Pressure Switch

Air flow and blocked vent status are continuously 

monitored by the Mighty Therm2 ignition control, at 

the control’s PSW terminal.

At the start of an ignition sequence, if the ignition 

control sees power at PSW for 30 seconds, but the 

combustion blower has not yet been energized by the 

control (F1 and F2), the ignition control will remain 

in this fault mode, with the blower off. If the power to 

PSW is removed while there is still a call for heat, the 

ignition sequence will start again, but the main valves 

will not be energized until PSW sees power during the 

ignition sequence.

If the PSW signal is lost while the Mighty 

Therm2 is firing, the control will immediately de-

energize the gas valve terminal (MV). The blower will 

remain on for the post-purge period (45 seconds), and 

the control will continue to monitor the PSW input. 

If the signal is detected during the post-purge period, 

a normal trial for ignition will begin, starting with 

the 15-second pre-purge. If the signal is not detected 

during the post-purge, the control will lockout with the 

Summary of Contents for Mighty Therm 2 MT2H

Page 1: ...r installation and or operation will void the warranty For indoor installations as an additional measure of safety Laars strongly recommends installation of suitable Carbon Monoxide detectors in the v...

Page 2: ...16 SECTION 4B Water Connections Water Heater 4B 1 Water System Piping Water Heater 20 4B 2 Hot Water Supply Piping Water Heater 20 4B 3 Water Flow Requirements Water Heater 20 4B 4 Combined Water pota...

Page 3: ...da the Canadian Electrical Code Part 1 CSA STD C22 1 and all applicable local codes as required by the AHJ This appliance must be electrically grounded in accordance with the applicable codes and stan...

Page 4: ...e installer Shipping costs are not included in the warranty coverage Some accessory items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything...

Page 5: ...ions may be on top or back of the Mighty Therm2 and are field convertible Model A Combustion Air Connection B Vent Connection C Horizontal Cat III Vent Pipe Size in cm in cm in cm in cm 200 20 5 52 4...

Page 6: ...may be on top or back of the Mighty Therm2 and are field convertible Model A Combustion Air Connection B Vent Connection C Horizontal Cat III Vent Pipe Size in cm in cm in cm in cm 200 20 5 52 4 10 5...

Page 7: ...Material Recommended Service Access Clearance inches cm inches cm Left Side 1 2 5 24 61 Right Side 1 2 5 24 61 Top 1 2 5 12 30 Back 1 2 5 12 30 Front 1 2 5 36 91 Vertical Category 1 Vent 6 15 2 Horiz...

Page 8: ...e outdoors or when communicating to the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4000 Btu hr 5 5 square cm kW of total input rating of all equip...

Page 9: ...ting it may be considered a Category I or a Category III appliance In general a vertical vent system will be a Category I system However in rare instances a Mighty Therm2 s vertical vent system may be...

Page 10: ...perating instructions on all appliances to be common vented for instructions warnings restrictions and safety requirements If safe operation of all appliances connected to a common vent cannot be assu...

Page 11: ...to non mechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inches 91 cm to any other appliance to side...

Page 12: ...addition the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling building o...

Page 13: ...combustion air terminal so that it cannot be blocked by snow The National Fuel Gas Code requires that it be at least 12 inches 30 cm above grade but the installer may determine it should be higher dep...

Page 14: ...tes et les fen tres du b timent et toutes les portes entre l espace o les appareils toujours raccord s au syst me d vacuation sont install s et les autres espaces du b timent Mettre en marche les s ch...

Page 15: ...sediment trap must be provided upstream of the gas controls 7 All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas 8 The appliance and its individu...

Page 16: ...coils located in air handling appliances where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of...

Page 17: ...minute H L head loss ft head loss in feet m head loss in meters Maximum temperature rise is 35 F 19 C as shown Head loss is for boiler s heat exchanger only N R not recommended Table 8 Water Flow Requ...

Page 18: ...LAARS Heating Systems Page 18 Figure 5 Hydronic Piping Multiple Boilers Low Temperature System Figure 6 Hydronic Piping One Boiler Multi Temperature System...

Page 19: ...Mighty Therm2 200 300 400 Page 19 Figure 7 Hydronic Piping Primary Secondary Reverse Return Figure 8 Hydronic Piping Primary Secondary Reverse Return Low Temperature...

Page 20: ...Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 of suitable discharge capacity must be installed in the separate storage tank system If the Mighty Therm2 water heater is installed...

Page 21: ...or the water is not able to circulate there is a risk of freezing in the heater or in the pipes in the system When water freezes it expands This can result in bursting of pipes in the system or damag...

Page 22: ...SOFT N NORMAL H HARD 1 THROUGH 7 5 7 6 THROUGH 17 OVER 17 2 3 4 Figure 10 Water Heater Piping Multiple Heaters One Tank SUPPLY RECIRC CWMU CAUTION THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AN...

Page 23: ...ANSION TANK 3 WAY VALVE VALVE PRESSURE REDUCING VALVE PUMP PRV TPRV Figure 12 Water Heater Piping Multiple Heaters Multiple Tanks CAUTION THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING...

Page 24: ...BK BL Y R BL W Y BLK BL R W W Y BLK GY V BK GY BK GY BK V W V W BR R BR BK BR BLK BR BLK R BK R BK BR BK BR R Y R G G G G BK W W W POWER BK BK BK BK BK BK BK BK BL R BL R BK STAGE 2 GAS VALVE STAGE 1...

Page 25: ...ral wires are provided for connections inside the boiler jacket Ground wire can be connected to the grounding screw in the box Wiring diagrams are shown in Figures 15 16 5 2 Field Wiring Field Install...

Page 26: ...r insures that water is at the highest point in the circulating loop then the system is ready for operation 14 Refer to local codes and the make up water valve manufacturer s instructions as to whethe...

Page 27: ...DE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases Th...

Page 28: ...ust plenum This switch opens if the pressure is excessive as an indicator of a blocked vent When these two pressure switches are closed voltage is sent to the PSW terminal on the ignition control whic...

Page 29: ...n the Burner Safety Shutoff Device must be tested To test a Close gas shutoff valve with burner operating b The flame will go out and blower will continue to run for the post purge cycle Three attempt...

Page 30: ...when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Attention Lors d entretien ou de r paration des commandes tiquetez tous les c...

Page 31: ...le switch with a remote bulb type sensor Switches for water heaters and low temperature boiler models are set at 200 F Switches for standard boilers are set at 240 F The control is located behind the...

Page 32: ...with sufficient air for complete combustion and black carbon sooting is seldom experienced If sooting is suspected view ports for inspection of the heat exchanger are provided on the side of the boil...

Page 33: ...cling Boiler Boiler short cycling is caused when the load on the boiler system swings rapidly causing frequent cycling between call for heat and satisfied conditions This condition is greatly reduced...

Page 34: ...ent Flue 2C2300 2C2300 2C2300 18 Assembly Air Shutter Blower 2C5000 2C5000 2C5000 19 Assembly Filter Housing 2C3800 2C3800 2C3800 20 Media Filter R2073200 R2073200 R2073200 21 Clip Retaining Filter Me...

Page 35: ...r Copper R2C4100 R3C4100 R4C4100 Assembly Tube Heat Exchanger Copper Nickel R2C4120 R3C4120 R4C4120 61 Header Inlet Outlet 2F4122 2F4122 2F4122 62 Header Return 2C4103 2C4103 2C4103 63 Chamber Header...

Page 36: ...7004 2C7004 2C7004 93 Switch Pressure Diaphragm SPST E0255500 E0255500 E0255500 94 Switch Pressure Diaphragm SPDT RE0240900 RE0240900 RE0240900 95 Switch Limit High Temperature Hydronic E2304800 E2304...

Page 37: ...Mighty Therm2 200 300 400 Page 37 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 22 23 24 25 26 27 28 29 30 31 31 31 31 31 32 20 21 19 Figure 20 Combustion Chamber Components...

Page 38: ...LAARS Heating Systems Page 38 Figure 21 Jacket Components 40 41 42 48 51 43 44 45 46 47 49 50 52 53 54 54 55...

Page 39: ...Mighty Therm2 200 300 400 Page 39 60 62 63 63 64 64 73 65 66 67 70 68 72 69B 69A 61 71 Figure 22 Heat Exchanger Components...

Page 40: ...LAARS Heating Systems Page 40 80 81 85 84 84 86 87 ON OFF 80 82 83 85 86 86 2 STAGE Figure 23 Gas Train Components...

Page 41: ...Mighty Therm2 200 300 400 Page 41 102 104 106 97 Figure 24 Control Panel Components...

Page 42: ...hester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1209 Document 1231B D...

Reviews: