SECTION 3.
Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not by the appliance.
The Mighty Therm2’s gas train allows the user to
pipe the gas from either the right side or the left side
of the unit. As shipped, the right side of the gas train is
capped off, and there is a manual valve on the left side.
If desired, the manual valve on the left side of the gas
train may be moved to the right side, and the cap on
the right side may be moved to the left.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Mighty
Therm2 appliances are equipped to operate at
elevations up to 10,000 feet (3050m). Mighty
Therm2 appliances may be adjusted to operate
properly at altitudes above 2500 feet (see Section
6.5.2) and the input will be reduced if the heating
value of the gas supply is below sea level values.
2. The maximum inlet gas pressure must not
exceed 13" w.c. (3.2kPa). The minimum inlet gas
pressure is 5 in. w.c. (1.2 kPa).
3. Refer to
Table 7
, size supply.
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
7. All threaded joints should be coated with
piping compound resistant to action of liquefied
petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 0.5 psig (3.45 kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 0.5 psig (3.45 kpa).
10. The appliance and its gas connection must be
leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Do not use open flame to check for leaks.
An open flame could lead to explosion, which
could result in property damage, serious injury
or death.
AVERTISSEMENT
Ne recherchez pas les fuites avec une flamme
nue. Une flamme nue peut provoquer une
explosion qui peut causer des dommages
matériels, de sérieuses blessures corporelles
ou la mort.
Distance from Gas Meter or Last Stage Regulator
Model and
Gas Type
0-100'
0-31 m
100-200'
31-61m
200-300'
61-91m
200 natural
1¼"
3.2 cm
1¼"
3.2 cm
1¼"
3.2 cm
200 propane
1"
2.5 cm
1"
2.5 cm
1¼"
3.2 cm
300 natural
1¼"
3.2 cm
1½"
4.0 cm
1½"
4.0 cm
300 propane
1
2.5 cm
1¼"
3.2 cm
1¼"
3.2 cm
400 natural
1¼"
3.2 cm
1½"
4.0 cm
2"
5.0 cm
400 propane
1¼"
3.2 cm
1¼"
3.2 cm
1½"
4.0 cm
Notes:
1. These figures are based on 1/2" (0.12 kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing
.
Table 7. Gas Piping Size.