LAARS Heating Systems

Page 10

 WARNING

Operation of appliances with a blocked common 

vent may lead to serious injury or death. Safety

devices must be implemented to prevent blocked 

common vent operation. If safe operation of all

appliances connected to a common vent cannot 

be assured, including prevention of spillage of 

flue gasses into living spaces, common venting 

should not be applied, and appliances should 

each be vented separately.

 AVERTISSEMENT

Le fonctionnement d’appareils connectés à 

un évent commun bouché peut provoquer de 

sérieuses blessures corporelles ou la mort. 

Des dispositifs de sécurité doivent être mis en 

place pour empêcher que les appareils soient 

utilisés avec un évent commun bouché. Si un 

fonctionnement sécuritaire de tous les appareils 

reliés à un évent commun et si la prévention des 

dégagements accidentels de gaz de combustion 

dans des zones habitées ne peuvent pas être 

assurés, un évent commun ne doit pas être mis 

en place et les appareils doivent être munis 

d’évents individuels séparés. 

It is for this reason that, in addition to 

following proper vent sizing, construction and safety 

requirements from the National Fuel Gas Code, 

ANSI Z223.1 or in Canada, from the Natural Gas 

and Propane Installation Code (CSA B149.1) as 

well as all applicable local codes, it is required that 

installers provide some means to prevent operation 

with a blocked common vent. It is suggested that a 

blocked vent safety system be employed such that if 

the switch from one appliance trips due to excessive 

stack spill or back pressure indicating a blocked vent 

condition, that all appliances attached to the vent be 

locked out and prevented from operating. Note that 

the Mighty Therm2 is equipped with a blocked vent 

safety (pressure) switch, as shipped. However, this 

safety switch has only been designed and tested to be 

effective in installations where the Mighty Therm2 

is vented separately and NOT common vented with 

other appliances. As an additional precaution, it is 

recommended that a Carbon Monoxide (CO) alarm be 

installed in all enclosed spaces containing combustion 

appliances. If assistance is required in determining 

how a blocked vent safety system should be connected 

to a LAARS product, please call Applications 

Engineering at the Rochester phone number on the 

back cover of this manual.

Refer to the installation and operating 

instructions on all appliances to be common vented 

for instructions, warnings, restrictions and safety 

requirements. If safe operation of all appliances 

connected to a common vent cannot be assured, 

including prevention of spillage of flue gases into 

living spaces, common venting should not be applied, 

and appliances should each be vented separately.

2.2.4  Category III Vent

When the Mighty Therm2 is vented with 

horizontal discharge, it must be installed per 

this installation manual and the venting system 

manufacturer’s installation instructions. The vent 

system must be sealed stainless steel, 

per Table 5

.

Term

Description

Pipe

Must comply with UL Standard 1738 such 

as Type AL29-4C Stainless Steel

(either insulated or non-insulated).

Joint  

Sealing

Follow vent manufacturer's instructions.

Table 5. Required Horizontal Venting Material.

       Route the vent pipe to the heater as directly as 

possible. Seal all joints and provide adequate hangers 

as required in the venting system manufacturer’s 

installation instructions. Horizontal portions of the 

venting system must be supported to prevent sagging 

and may not have any low sections that could trap 

condensate.

The unit must not support the weight of the vent 

pipe. Horizontal runs must slope downwards not less 

than ¼ inch per foot (2 cm/m) from the unit to the vent 

terminal.

L’appareil ne doit pas supporter le poids de la 

gaine d’évent. Les parties horizontales doivent être 

installées avec une pente de 2 cm/m (1/4 inch par pied) 

descendant de l’appareil vers la sortie de l’évent.

Reference Table 1 for the size of the Category 

III vent system. Up to three elbows can be used with 

50 linear feet (15.2m) of pipe. Subtract 10 allowable 

linear feet (3.0m) for every additional elbow used.

2.3  Locating Vent & Combustion Air 

Terminals

2.3.1  Side Wall Vent Terminal

The appropriate Laars side wall vent terminal 

must be used, and is listed in the installation and 

operation manual.  The terminal provides a means of 

installing the vent piping through the building wall, 

and must be located in accordance with ANSI Z223.1/

NFPA 54 and applicable local codes.  In Canada, the 

installation must be in accordance with CSA B149.1 

and local applicable codes.  Consider the following 

when installing the terminal:

1. 

Figure 3 

shows the requirements for mechanical 

vent terminal clearances for the U.S. and Canada.

2.  Locate the vent terminal so that vent gases cannot 

be drawn into air conditioning system inlets.

3.  Locate the vent terminal so that vent gases cannot 

enter the building through doors, windows, 

Summary of Contents for Mighty Therm 2 MT2H

Page 1: ...r installation and or operation will void the warranty For indoor installations as an additional measure of safety Laars strongly recommends installation of suitable Carbon Monoxide detectors in the v...

Page 2: ...16 SECTION 4B Water Connections Water Heater 4B 1 Water System Piping Water Heater 20 4B 2 Hot Water Supply Piping Water Heater 20 4B 3 Water Flow Requirements Water Heater 20 4B 4 Combined Water pota...

Page 3: ...da the Canadian Electrical Code Part 1 CSA STD C22 1 and all applicable local codes as required by the AHJ This appliance must be electrically grounded in accordance with the applicable codes and stan...

Page 4: ...e installer Shipping costs are not included in the warranty coverage Some accessory items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything...

Page 5: ...ions may be on top or back of the Mighty Therm2 and are field convertible Model A Combustion Air Connection B Vent Connection C Horizontal Cat III Vent Pipe Size in cm in cm in cm in cm 200 20 5 52 4...

Page 6: ...may be on top or back of the Mighty Therm2 and are field convertible Model A Combustion Air Connection B Vent Connection C Horizontal Cat III Vent Pipe Size in cm in cm in cm in cm 200 20 5 52 4 10 5...

Page 7: ...Material Recommended Service Access Clearance inches cm inches cm Left Side 1 2 5 24 61 Right Side 1 2 5 24 61 Top 1 2 5 12 30 Back 1 2 5 12 30 Front 1 2 5 36 91 Vertical Category 1 Vent 6 15 2 Horiz...

Page 8: ...e outdoors or when communicating to the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4000 Btu hr 5 5 square cm kW of total input rating of all equip...

Page 9: ...ting it may be considered a Category I or a Category III appliance In general a vertical vent system will be a Category I system However in rare instances a Mighty Therm2 s vertical vent system may be...

Page 10: ...perating instructions on all appliances to be common vented for instructions warnings restrictions and safety requirements If safe operation of all appliances connected to a common vent cannot be assu...

Page 11: ...to non mechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inches 91 cm to any other appliance to side...

Page 12: ...addition the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling building o...

Page 13: ...combustion air terminal so that it cannot be blocked by snow The National Fuel Gas Code requires that it be at least 12 inches 30 cm above grade but the installer may determine it should be higher dep...

Page 14: ...tes et les fen tres du b timent et toutes les portes entre l espace o les appareils toujours raccord s au syst me d vacuation sont install s et les autres espaces du b timent Mettre en marche les s ch...

Page 15: ...sediment trap must be provided upstream of the gas controls 7 All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas 8 The appliance and its individu...

Page 16: ...coils located in air handling appliances where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of...

Page 17: ...minute H L head loss ft head loss in feet m head loss in meters Maximum temperature rise is 35 F 19 C as shown Head loss is for boiler s heat exchanger only N R not recommended Table 8 Water Flow Requ...

Page 18: ...LAARS Heating Systems Page 18 Figure 5 Hydronic Piping Multiple Boilers Low Temperature System Figure 6 Hydronic Piping One Boiler Multi Temperature System...

Page 19: ...Mighty Therm2 200 300 400 Page 19 Figure 7 Hydronic Piping Primary Secondary Reverse Return Figure 8 Hydronic Piping Primary Secondary Reverse Return Low Temperature...

Page 20: ...Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 of suitable discharge capacity must be installed in the separate storage tank system If the Mighty Therm2 water heater is installed...

Page 21: ...or the water is not able to circulate there is a risk of freezing in the heater or in the pipes in the system When water freezes it expands This can result in bursting of pipes in the system or damag...

Page 22: ...SOFT N NORMAL H HARD 1 THROUGH 7 5 7 6 THROUGH 17 OVER 17 2 3 4 Figure 10 Water Heater Piping Multiple Heaters One Tank SUPPLY RECIRC CWMU CAUTION THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AN...

Page 23: ...ANSION TANK 3 WAY VALVE VALVE PRESSURE REDUCING VALVE PUMP PRV TPRV Figure 12 Water Heater Piping Multiple Heaters Multiple Tanks CAUTION THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING...

Page 24: ...BK BL Y R BL W Y BLK BL R W W Y BLK GY V BK GY BK GY BK V W V W BR R BR BK BR BLK BR BLK R BK R BK BR BK BR R Y R G G G G BK W W W POWER BK BK BK BK BK BK BK BK BL R BL R BK STAGE 2 GAS VALVE STAGE 1...

Page 25: ...ral wires are provided for connections inside the boiler jacket Ground wire can be connected to the grounding screw in the box Wiring diagrams are shown in Figures 15 16 5 2 Field Wiring Field Install...

Page 26: ...r insures that water is at the highest point in the circulating loop then the system is ready for operation 14 Refer to local codes and the make up water valve manufacturer s instructions as to whethe...

Page 27: ...DE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases Th...

Page 28: ...ust plenum This switch opens if the pressure is excessive as an indicator of a blocked vent When these two pressure switches are closed voltage is sent to the PSW terminal on the ignition control whic...

Page 29: ...n the Burner Safety Shutoff Device must be tested To test a Close gas shutoff valve with burner operating b The flame will go out and blower will continue to run for the post purge cycle Three attempt...

Page 30: ...when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Attention Lors d entretien ou de r paration des commandes tiquetez tous les c...

Page 31: ...le switch with a remote bulb type sensor Switches for water heaters and low temperature boiler models are set at 200 F Switches for standard boilers are set at 240 F The control is located behind the...

Page 32: ...with sufficient air for complete combustion and black carbon sooting is seldom experienced If sooting is suspected view ports for inspection of the heat exchanger are provided on the side of the boil...

Page 33: ...cling Boiler Boiler short cycling is caused when the load on the boiler system swings rapidly causing frequent cycling between call for heat and satisfied conditions This condition is greatly reduced...

Page 34: ...ent Flue 2C2300 2C2300 2C2300 18 Assembly Air Shutter Blower 2C5000 2C5000 2C5000 19 Assembly Filter Housing 2C3800 2C3800 2C3800 20 Media Filter R2073200 R2073200 R2073200 21 Clip Retaining Filter Me...

Page 35: ...r Copper R2C4100 R3C4100 R4C4100 Assembly Tube Heat Exchanger Copper Nickel R2C4120 R3C4120 R4C4120 61 Header Inlet Outlet 2F4122 2F4122 2F4122 62 Header Return 2C4103 2C4103 2C4103 63 Chamber Header...

Page 36: ...7004 2C7004 2C7004 93 Switch Pressure Diaphragm SPST E0255500 E0255500 E0255500 94 Switch Pressure Diaphragm SPDT RE0240900 RE0240900 RE0240900 95 Switch Limit High Temperature Hydronic E2304800 E2304...

Page 37: ...Mighty Therm2 200 300 400 Page 37 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 22 23 24 25 26 27 28 29 30 31 31 31 31 31 32 20 21 19 Figure 20 Combustion Chamber Components...

Page 38: ...LAARS Heating Systems Page 38 Figure 21 Jacket Components 40 41 42 48 51 43 44 45 46 47 49 50 52 53 54 54 55...

Page 39: ...Mighty Therm2 200 300 400 Page 39 60 62 63 63 64 64 73 65 66 67 70 68 72 69B 69A 61 71 Figure 22 Heat Exchanger Components...

Page 40: ...LAARS Heating Systems Page 40 80 81 85 84 84 86 87 ON OFF 80 82 83 85 86 86 2 STAGE Figure 23 Gas Train Components...

Page 41: ...Mighty Therm2 200 300 400 Page 41 102 104 106 97 Figure 24 Control Panel Components...

Page 42: ...hester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1209 Document 1231B D...

Reviews: