Mighty Therm
2
(200, 300, 400)
Page 17
Model
(Size)
20°F
25°F
30°F
35°F
flow
gpm
H/L
feet
flow
gpm
H/L
feet
flow
gpm
H/L
feet
flow
gpm
H/L
feet
200
17
1.6
14
1.0
11
0.7
10
0.5
300
26
3.5
20
2.3
17
1.6
15
1.2
400
34
6.3
27
4.0
23
2.8
19
2.1
Metric Equivalent
Model
(Size)
11°C
14°C
17°C
19°C
flow
lpm
H/L
m
flow
lpm
H/L
m
flow
lpm
H/L
m
flow
lpm
H/L
m
200
64
0.5
51
0.3
43
0.2
37
0.2
300
97
1.1
77
0.7
64
0.5
55
0.4
400
129
1.9
103
1.2
86
0.9
74
0.6
Notes:
gpm = gallons per minute, lpm = liters per minute,
H/L = head loss, ft = head loss in feet,
m = head loss in meters.
Maximum temperature rise is 35°F (19°C), as shown.
Head loss is for boiler’s heat exchanger only.
N/R = not recommended.
Table 8. Water Flow Requirements - MT2H.
Figure 4. Hydronic Piping — Multiple Boilers, Primary Secondary System.
IMPORTANT NOTES:
Different glycol products
may provide varying degrees of protection.
Glycol products must be maintained properly in a
heating system, or they may become ineffective.
Consult the glycol specifications, or the glycol
manufacturer, for information about specific
products, maintenance of solutions, and set up
according to your particular conditions. Never use
ethylene
glycol (automotive antifreeze).