Description
1: EH
Error history up to 10
Check last 10 error codes (E0 - E9)
2: cE
Delete Error history
Select “ON” to delete error code history
Range: ON or OFF,Default OFF
3: In
System initialize
Select “ON” to reset to factory setting,Default OFF
4: OH
Maximum Outdoor
Temperature
When used with an outdoor sensor, sets the maximum outdoor design
temperature for the system design. Warm weather shut down will
disable the appliance if the programmed outdoor temperature is ex-
ceeded. Maximum outdoor temperature must be set at least 9°F above
the minimum outdoor temperature. Range: (Minimum Outdoor Tempera-
ture + 9°F) to 110°F , Default 68°F
5: OL
Minimum Outdoor
Temperature
Sets the minimum outdoor design temperature for the system. Minimum
outdoor temperature must be set at least 9°F below the maximum
outdoor temperature.
Range: -4°F to (Maximum Outdoor Temperature - 9°F), Default 5°F
6: cH
Maximum Supply
temperature
Sets the maximum design supply temperature based on the minimum
outdoor design temperature. Maximum supply temperature must be set
at least 9oF above the minimum supply temperature. Range: (Minimum
Supply Tempe 9°F) - 180°F, Default 180°F
To c hange any of the Installer Parameters,
Start by turning
OFF
the Power
to the
Display Control.
Then, with the power OFF, Press and HOLD (more than 5 seconds) the Button B
to get into the Installer Mode.
Rotate Dial E until you find the Installer Parameter (full list on facing page) that you wish to change. Tap Dial E
to enter that Parameter.
Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.
Finish by pressing button B
B
C
E
A
D
Summary of Contents for mascot ft MFTHW
Page 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Page 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Page 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Page 81: ...Mascot FT Heating Only Boiler Page 79 ...
Page 83: ...Mascot FT Heating Only Boiler Page 81 ...
Page 85: ...Mascot FT Heating Only Boiler Page 83 ...
Page 87: ...Mascot FT Heating Only Boiler Page 85 ...
Page 89: ...Mascot FT Heating Only Boiler Page 87 ...
Page 91: ...Mascot FT Heating Only Boiler Page 89 ...
Page 93: ...Mascot FT Heating Only Boiler Page 91 ...
Page 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Page 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...