5.7 Installer Mode (continued)
30:Cr
Auto
Automatic rotation
The first unit to operate when there is a T/T call is the unit
that ran the least amount of time during the prior heat calls.
Cr:Ct
Cascade Rotation time
Cascade Rotation time
Range: 0-240 Hours, Default 48 Hours
31: Ct
Cascade System
temperature
Cascade System temperature:
Range: 9°F – 180°F, Default 180°F
32: Cd
Cascade System
Temperature Differential
(burner ON)
Cascade System Temperature Differential (burner ON)
Range: 5°F-30°F, Default 10°F
33: HA
High Elevation Mode
High Elevation Mode ( 0-2, 2-5, 5-8, 8-10 ),
Default HA 0
34:AP
AP:cP
Internal CH Pump, CH
Pump and DHW Indirect
Pump Test Mode
This function sets the time to run both the Internal CH and
Internal DHW Storage pumps to purge air from the system.
Range: 1 – 30 minutes,Default 5
P1:oF or
P1:on
Internal CH Pump and
CH Pump Test Mode
Turn this function on to activate Internal CH and CH pump
testing. Only works in installation mode. Turns off when in
normal mode. Default OFF
P2:oF
or
P2:on
Internal CH Pump and
DHW Indirect Pump Test
Mode
Turn this function on to activate Internal CH and DHW
Indirect pump testing.
Only works in installation mode. Turns off when in normal
mode. Default OFF
35: SS
SS:Sd
Allows the user to set the
year of next service
reminder
Allows the user to set the year of next service reminder
XX / XX / XXXX (MONTH / DAY / YEAR)
SS: br
Allows the user to set the
service reminder based
on BURNER RUN HOURS
Allows the user to set the service reminder based on
BURNER RUN HOURS
(0: OFF, 1~9000Hours) , Default 0
36: UC
FAH(°F)
Allows the user to
change the unit
Allows the user to change the unit
Range: °F or °C
CEL(°C)
37: CM OFF
CH Step Modulation
Allows the user to turn ON the step modulation, which
regulates burner output in six steps at one minute intervals.
Step modulation will start at the last modulation rate of the
boiler and work up one minute at a time.
Default: OFF (Selection: OFF or ON).
38: dM OFF
DHW Step Modulation
39: SA
AquA
Select Aquastate
(contact) Type
This mode is aquastate (contact) type.
SEnS
Select DHW NTC
Sensor Type
This mode is NTC sensor type.
40: BP ON
Boiler Pump
Allows to turn off boiler pump during DHW call.
Index
Numbers
Parameter
Description
27: Cn
Cascade Number
Cascade Number
Range: 0 (Master), 1(slave 1), …., 19(slave 19)
“29: CP” has to be set with the total number of units in the
cascade before “28: Cn” can be set. Default 0
28: CP
Cascade Parameter
Number of units cascaded
Range: 1- 20 , Default 1
29: Eh
Common Vent
Common Vent
Range: ON / OFF, Default OFF
Summary of Contents for mascot ft MFTHW
Page 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Page 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Page 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Page 81: ...Mascot FT Heating Only Boiler Page 79 ...
Page 83: ...Mascot FT Heating Only Boiler Page 81 ...
Page 85: ...Mascot FT Heating Only Boiler Page 83 ...
Page 87: ...Mascot FT Heating Only Boiler Page 85 ...
Page 89: ...Mascot FT Heating Only Boiler Page 87 ...
Page 91: ...Mascot FT Heating Only Boiler Page 89 ...
Page 93: ...Mascot FT Heating Only Boiler Page 91 ...
Page 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Page 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...