4.16 Disposal of Condensate
1
2
3
4
Condensate
drain pipe
Condensate
Trap
High efficiency gas condensing Boilers create
condensation when operating. Condensation has
acidic (pH) of approximately 4-5.
Condensate must be drained in accordance with all
local regulations. Follow your local code with regards
to the disposal of condensation.
One of 4 disposal methods must be followed
1. to floor drain
2. to neutralizer (optional kit)
3. to laundry tub
4. to condensate pump (field supplied)
If a neutralizer is installed, periodic replacement of the
lime stone (or neutralizing agent) will be required. The
rate of depletion of the lime stone varies upon usage
of the boiler. During the first year of operation, please
check the neutralizer every few months for depletion.
Apply only corrosion-resistant materials for the
condensate drain lines such as 1/2˝ PVC, CPVC,
Polypropylene pipe or included plastic hose.
NOTICE
For Category II and IV boilers, be installed so as to
prevent accumulation of condensate; and
For Category II and IV boilers, where necessary, have
means provided for drainage of condensate.
AVIS
les chaudières de catégories II et IV doivent être
installées de façon à empêcher l'accumulation de
condensat; et
si nécessaire, les chaudières de catégories II et IV
doivent être pourvues de dispositifs d'évacuation du
condensat.
CAUTION
Condensate is mildly acidic (pH=5), and may harm
some floor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe, and
anything that will come in contact with the condensate
can withstand the acidity, or neutralize the condensate
before disposal.
Damage caused by failure to install
a neutralizer kit or to adequately treat condensate
will not be the manufacturer’s responsibility.
Contact Laars to order
Neutralizer Kit# A2123601
_________________________________________
Figure 13. Various condensate disposal methods
Summary of Contents for mascot ft MFTHW
Page 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Page 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Page 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Page 81: ...Mascot FT Heating Only Boiler Page 79 ...
Page 83: ...Mascot FT Heating Only Boiler Page 81 ...
Page 85: ...Mascot FT Heating Only Boiler Page 83 ...
Page 87: ...Mascot FT Heating Only Boiler Page 85 ...
Page 89: ...Mascot FT Heating Only Boiler Page 87 ...
Page 91: ...Mascot FT Heating Only Boiler Page 89 ...
Page 93: ...Mascot FT Heating Only Boiler Page 91 ...
Page 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Page 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...