LAARS Heating Systems
Page 26
4.7.3 Indoor Combustion Air
Read and Follow Sections 4.3 Guidelines First.
1. Insert the termination end cap into the intake air duct.
2. Provide two openings to allow for circulation of
combustion air as specified by ANSI Z224.1/NFPA 54.
In Canada refer to CAN/CSA B-149.1
NOTE: The Mascot FT needs fresh air for safe operation and
must be installed so there are provisions for adequate
combustion and ventilation air.
Model
MFTHW80
MFTHW100
MFTHW120
MFTHW140
MFTHW199
Maximum Input (BTU/H)
80,000
100,000
120,000
140,000
199,000
Indoor make up air is provided,
a minimum free area of 1 in2
per 1,000 BTU/H
80 in
2
13 1/4˝
(W) x 13 1/4˝ (H)
100 in
2
13 1/4˝
(W) x 13 1/4˝ (H)
120 in
2
13 1/4˝
(W) x 13 1/4˝ (H)
140 in
2
13 1/4˝
(W) x 13 1/4˝ (H)
199 in
2
13 1/4˝
(W) x 13 1/4˝ (H)
Table 7. Adequate Free Area
WARNING
• Use of cellular core CPVC, or Radel (polyphenolsulfone)
in venting systems is prohibited.
• Covering non-metallic vent pipe and fittings with thermal
insulation is prohibited.
• Do not obstruct the flow of combustion and ventilated air.
Summary of Contents for mascot ft MFTHW
Page 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Page 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Page 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Page 81: ...Mascot FT Heating Only Boiler Page 79 ...
Page 83: ...Mascot FT Heating Only Boiler Page 81 ...
Page 85: ...Mascot FT Heating Only Boiler Page 83 ...
Page 87: ...Mascot FT Heating Only Boiler Page 85 ...
Page 89: ...Mascot FT Heating Only Boiler Page 87 ...
Page 91: ...Mascot FT Heating Only Boiler Page 89 ...
Page 93: ...Mascot FT Heating Only Boiler Page 91 ...
Page 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Page 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...