background image

Page 14

a bypass plug must be installed in the fuel pump.
The plug is supplied with the oil burner. There is
a decal located on the fuel pump showing where
the bypass plug goes.

If a fuel unit is set up for a two-pipe system, but
is actually connected to a one-pipe system, the
pressure in the fuel pump builds up to over 300
psi when the burner turns on. This will cause the
motor to bind and stop running or ruin the pump
seals, or both,

2.

An oil filter must be installed on the inlet line. A
very small amount of dirt in the oil can plug the
nozzle. A properly sized oil filter is shipped with
the heater (see Fig. 11).

3.

Is there oil in the storage tank?

4.

Are all of the shut-off valves on the oil lines
open?

5.

Are the fuel lines adequately sized according to
the table on page 5?

6.

Are there any leaks in the fuel line? A very small
leak can cause the fuel pump to suck air into the
system, resulting in failure to operate or a
pulsating, noisy fire.

7.

Is the unit properly grounded electrically? This is
extremely important. Use of PVC piping in the
pool filter system prevents grounding through the
piping.

8.

If a time clock is installed, is there power to the
timer? Is the timer motor working? There is
usually a visual motor check opening on the timer
mechanism. Is the switch located below the timer
dial “ON”?

9.

Are there any loose wires or terminals?

10.

Is the pool filter clean, and is the pump operating
properly?

4D. Operating Sequence

When every part of the system is working

properly, the heater will go through the following
sequence:

1.

When the filter pump builds up enough pressure
in the piping, the contacts in the heater pressure
switch close.

2.

The heater thermostat calls for heat completing
the circuit between the two thermostat terminals
on the primary control of the oil burner.

3.

The primary safety control on the oil burner goes
through a self-test sequence. One of the steps in
the sequence is to check out the cadmium cell
flame detector. If the cad cell senses light, the

burner will not fire. If everything checks out, the
burner motor and ignition transformer are
powered.

On 60Hz models, the ignition transformer

operates during the entire burner operation.

4.

If the cad cell does not sense a good flame within
30 seconds the primary control de-energizes the
motor and ignition transformer. This turns off the
heater. It can be manually restarted by pushing
the reset button after waiting about one minute.

5.

During the period when the filter pump is
running, which is set by the time clock, the
thermostat will turn the burner on and off as
required to maintain the water temperature set on
the thermostat.

6.

If a time clock is used, the contacts in the
Fireman switch open about 20 minutes before the
pool filter cycle is completed. This shuts off the
oil burner. The oil burner cannot be restarted
during this period. The filter pump continues to
run for another 20 minutes, transferring any heat
stored in the firebox to the pool.

4E. Troubleshooting

NOTE: These troubleshooting procedures

require connections to electrical terminals and jumper
wires to check operation. To avoid electrical shock,
turn off electric power before servicing line voltage
controls. Never leave a jumper wire in place to fix a
heater. This would bypass safety and operating
controls.

4E-1. Burner will not start (motor and

transformer do not come on)

Figure 20. Cad Cella and Primary Control.

Summary of Contents for DP2000

Page 1: ...or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT T...

Page 2: ...re 10 3B Setting the Time Clock 11 3C Winter Shutdown 12 3D Periodic Maintenance 12 SECTION 4 Maintenance 4A Trouble Shooting 12 4B Cleaning the Heat Exchanger 13 4C Trouble Shooting Guide 13 4D Opera...

Page 3: ...s and packages the heater before delivering it to the freight carrier Immediately file any claim for damage against the freight carrier 2B Assembly and Location Only use the XL 3 heater with pools fil...

Page 4: ...prove access for service and maintenance Make the change before locating and connecting the heater Follow these step by step instructions and Figure 3 to reverse the heat exchanger 1 Remove the contro...

Page 5: ...nd connect it to the header where the drain plug was removed 18 Replace the gap spacers siphon loop cover and rubber plugs and grommets 19 Install the T baffles on the gap spacers to match the screw h...

Page 6: ...ny change in the amount of draft in the combustion chamber can affect the flame characteristics An approved barometric draft control must be used on all indoor installations to maintain a clean and co...

Page 7: ...n on the decal on the end of the fuel unit Remove the large hex head fitting and insert the plug Figure 9 Combustion Air Indoor Installation Lift from bottom of Storage tank to Total Tubing Length All...

Page 8: ...aded 1 1 4 iron pipe or 1 1 2 copper tubing see Fig 12 Connect the pool heater between the pump and filter and the pool or spa If the system flow rate exceeds 60 gpm 228 lpm install a manual bypass va...

Page 9: ...warranty IMPORTANT 1 Provide the automatic chlorinator with an anti siphoningdevicetopreventchlorinesiphoning into the heater after the pump shuts off 2 Wire the electric chlorinator so it cannot ope...

Page 10: ...ol compartment The wirenut has a tag on it carrying wiring instructions Position the field installed wires away from the inner panel 2K Special Pressure Switch A special pressure switch is required if...

Page 11: ...ry three more re sets If there is still no ignition have a qualified oil service technician bleed the fuel line and check for ignition problems When the heater does fire oil which is in the firebox wi...

Page 12: ...y fouling the external heat exchanger passages causing incompletecombustion 3D Periodic Maintenance Oil the oil burner motor every six months Use SAE 30 non detergent motor oil in both holes Check the...

Page 13: ...Use a bottle brush to brush down between the tube fins toward the firebox The ash can be softened for easier removal by lightly dampening with a wet brush Do not let water get in the firebox 5 Reach...

Page 14: ...he piping the contacts in the heater pressure switch close 2 The heater thermostat calls for heat completing the circuit between the two thermostat terminals on the primary control of the oil burner 3...

Page 15: ...ing spark at the electrodes go to step 3 3 Lift the ignition transformer and make sure the motor rotates freely If it does not rotate freely replace the motor If the motor is internally binding replac...

Page 16: ...e heater will smoke Generally the C02 reading will be above 12 when not enough air is provided Lacking proper instruments a temporary fuel air adjustment can be made Close the end shutter and then slo...

Page 17: ...move one 2 000 ohm resistor wire from the primary control The primary should lock out on safety within 25 seconds 12 After the primary locks out the ohmmeter pointer should move to near the 50 mark on...

Page 18: ...KET COMPONENTS 49 Burner Tube Gasket All N0006600 50 Burner Support Bracket All 10392000 51 Burner Compartment Door 2000 10412203 51 Burner Compartment Door 3000 10412204 52 Fire Box Plug All T0020700...

Page 19: ...el DP Oil Fired Heater Page 19 51 53 52 1 49 50 63 62 29 26 46 44 47 34 12 13 20 21 11 4 22 30 33 32 25 27 37 36 25 29 55 54 56 57 58 59 60 8 9 5 7 6 30 64 29 18 39 40 42 15 19 31 24 17 23 43 45 61 48...

Page 20: ...eplacementofdefective parts and shall not include transportation to or from factory fieldlabor andconsequentialorincidentaldamages Ship inoperativepartsorcompleteheaterwithSerialNumberand purchasedate...

Reviews: