background image

Model DP Oil-Fired Heater

Page 17

2.

Replace the oil nozzle once a season (see the oil
burner Manual).

3.

Oil the burner motor every three months. Use
non- detergent #40 motor oil at both oil holes.

4.

Replace the in-line oil filter cartridge once a year.

SECTION 5.
Service Information

5A. Control and Cad Cell Tests

IMPORTANT: In the following test procedures:

1.

The 2,000 ohm resistor checks the calibration and
performance of the primary safety control.

2.

The ohm meter checks cad cell operation only.

Test Instructions

1.

Remove two thermostat wires from the primary
control.

2.

Push reset buttons on burner motor and primary
control.

3.

Remove two cad cell wires from primary control.

4.

Connect ohmmeter leads to cad cell wires.

5.

Set ohmmeter range to 1 KW.

6.

Connect resistor wires to cad cell terminals on the
Step 2. primary control.

7.

Place a jumper wire on the thermostat terminals
on the primary control.

8.

Loosen one cad cell terminal screw on the
primary control. Move the resistor wire slightly
to temporarily break contact. When the burner
starts, quickly tighten the terminal screw.

9.

Check combustion to make sure there is flame. If
there is no flame, open the thermostat jumper and
stop the test.

10.

The ohmmeter pointer should go to zero. If the
pointer stops between 2 and 3, that’s okay.

11.

After three minutes, remove one 2,000 ohm
resistor wire from the primary control. The
primary should lock out on safety within 25
seconds,

12.

After the primary locks out, the ohmmeter pointer
should move to near the 50 mark on the scale.

13.

Wait three minutes, then perform the following
steps in the right order:
a.

Remove the 2,000 ohm resistor from the
primary control.

b.

Remove the jumper wire from the primary
control thermostat terminals.

c.

Attach the cad cell wires to the primary
control.

d.

Attach the thermostat wires to the primary
control.

e.

Push the primary control reset button.

f.

Set the ohmmeter range to 100 MA when it
is not going to be used.

14.

Turn the heater thermostat all the way to the
right. The burner should start. Reset the
thermostat to the appropriate temperature.

5B. Control & Cad Cell

Trouble-Shooting Guide

Symptom

Possible Cause

Step 2.

Burner runs all the time

Defective primary
control

Step 8.

No  combustion

No power to the
primary.
Limit switch turned
off.
Defective limit
switch.
Bad wire connection.
Bad burner motor.
No power from fuse
box.
Defective primary

Step 10.

Ohmmeter pointer above 2.

Partly plugged
nozzle.
Cad cell dirty.
Cad cell misaligned.
Defective cell.

Ohmmeter pointer below 3

Not enough
combustion air.
Cad cell sees too
much light.
Adjust alignment.

Step 11.

Primary won’t lock out

Defective primary

Step 12.

Ohmmeter pointer below 50

Stray light in burner
housing.
Defective cad cell.

Step 14.

Burner won’t start

Open circuit in
thermostat wiring.
Dirty thermostat
contacts.
Defective thermostat.

Step 14.

Summary of Contents for DP2000

Page 1: ...or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT T...

Page 2: ...re 10 3B Setting the Time Clock 11 3C Winter Shutdown 12 3D Periodic Maintenance 12 SECTION 4 Maintenance 4A Trouble Shooting 12 4B Cleaning the Heat Exchanger 13 4C Trouble Shooting Guide 13 4D Opera...

Page 3: ...s and packages the heater before delivering it to the freight carrier Immediately file any claim for damage against the freight carrier 2B Assembly and Location Only use the XL 3 heater with pools fil...

Page 4: ...prove access for service and maintenance Make the change before locating and connecting the heater Follow these step by step instructions and Figure 3 to reverse the heat exchanger 1 Remove the contro...

Page 5: ...nd connect it to the header where the drain plug was removed 18 Replace the gap spacers siphon loop cover and rubber plugs and grommets 19 Install the T baffles on the gap spacers to match the screw h...

Page 6: ...ny change in the amount of draft in the combustion chamber can affect the flame characteristics An approved barometric draft control must be used on all indoor installations to maintain a clean and co...

Page 7: ...n on the decal on the end of the fuel unit Remove the large hex head fitting and insert the plug Figure 9 Combustion Air Indoor Installation Lift from bottom of Storage tank to Total Tubing Length All...

Page 8: ...aded 1 1 4 iron pipe or 1 1 2 copper tubing see Fig 12 Connect the pool heater between the pump and filter and the pool or spa If the system flow rate exceeds 60 gpm 228 lpm install a manual bypass va...

Page 9: ...warranty IMPORTANT 1 Provide the automatic chlorinator with an anti siphoningdevicetopreventchlorinesiphoning into the heater after the pump shuts off 2 Wire the electric chlorinator so it cannot ope...

Page 10: ...ol compartment The wirenut has a tag on it carrying wiring instructions Position the field installed wires away from the inner panel 2K Special Pressure Switch A special pressure switch is required if...

Page 11: ...ry three more re sets If there is still no ignition have a qualified oil service technician bleed the fuel line and check for ignition problems When the heater does fire oil which is in the firebox wi...

Page 12: ...y fouling the external heat exchanger passages causing incompletecombustion 3D Periodic Maintenance Oil the oil burner motor every six months Use SAE 30 non detergent motor oil in both holes Check the...

Page 13: ...Use a bottle brush to brush down between the tube fins toward the firebox The ash can be softened for easier removal by lightly dampening with a wet brush Do not let water get in the firebox 5 Reach...

Page 14: ...he piping the contacts in the heater pressure switch close 2 The heater thermostat calls for heat completing the circuit between the two thermostat terminals on the primary control of the oil burner 3...

Page 15: ...ing spark at the electrodes go to step 3 3 Lift the ignition transformer and make sure the motor rotates freely If it does not rotate freely replace the motor If the motor is internally binding replac...

Page 16: ...e heater will smoke Generally the C02 reading will be above 12 when not enough air is provided Lacking proper instruments a temporary fuel air adjustment can be made Close the end shutter and then slo...

Page 17: ...move one 2 000 ohm resistor wire from the primary control The primary should lock out on safety within 25 seconds 12 After the primary locks out the ohmmeter pointer should move to near the 50 mark on...

Page 18: ...KET COMPONENTS 49 Burner Tube Gasket All N0006600 50 Burner Support Bracket All 10392000 51 Burner Compartment Door 2000 10412203 51 Burner Compartment Door 3000 10412204 52 Fire Box Plug All T0020700...

Page 19: ...el DP Oil Fired Heater Page 19 51 53 52 1 49 50 63 62 29 26 46 44 47 34 12 13 20 21 11 4 22 30 33 32 25 27 37 36 25 29 55 54 56 57 58 59 60 8 9 5 7 6 30 64 29 18 39 40 42 15 19 31 24 17 23 43 45 61 48...

Page 20: ...eplacementofdefective parts and shall not include transportation to or from factory fieldlabor andconsequentialorincidentaldamages Ship inoperativepartsorcompleteheaterwithSerialNumberand purchasedate...

Reviews: