background image

19 

 

5.3 

Troubleshooting Chart 

 

         Isolate from all power sources prior to performing any interior verifications or part replacements. 

Symptom 

Possible Cause 

AC Breaker Trips Immediately 
(High Input Current) 

Wrong AC Input Voltage 
AC Input Taps on Power Transformer are Incorrectly Set 
Incorrect, Damaged or Loose Cable/Harness Connections 
DC Output Too High 
Defective Component on Heatsink Assembly 

DC Breaker Trips Immediately 

(High Output Current) 

Incorrect, Damaged or Loose Cable/Harness Connections 
Incorrect Battery Connected 
Shorted Output Cables 
Shorted Battery Cells or Customer Equipment 
Defective Component on Heatsink Assembly 

No Display and No LEDs 

No AC Voltage Applied to Charger 
Charger AC Breaker is open 
Incorrect, Damaged or Loose Cable/Harness Connections 
Defective Control/Display Board (S2A-368S) 

Failed LED Test 

Defective Control/Display Board (S2A-368S) 
Defective LEDs 

Meter Reading Incorrect  

Voltage or Current 

Incorrect, Damaged or Loose Cable/Harness Connections 
Incorrect Settings on Control Board 
Defective Shunt 
Defective Control Board (S2A-368S)  

Charger Running Hot 

Inadequate Ventilation 
Ambient is Too Hot 

Battery Temperature Too  
High 

Insufficient Cool Down Between Charges 
Battery Power Demand Too Great 
Battery Needs to be Equalized 

Erratic Operation 

Defective Control Board (S2A-368S) 
Incorrect, Damaged or Loose Cable/Harness Connections 
Defective Component on Heatsink Assembly 
Moisture Inside Cabinet 
Lack of Maintenance 
High Ambient Temperature 

Low Output Voltage  

or Current 

Output Voltage settings are Incorrect 
Charger is in Current Limit 
Defective Control Board (S2A-368S) 
Defective Component on Heatsink Assembly 

High Output Voltage  
or Current 

Output Voltage settings are Incorrect 

Defective Control Board (S2A-368S) 

Defective Component on Heatsink Assembly 

Ground Detection Fault 

(Positive Ground / Negative Ground) 

Isolate charger from DC system by removing all wires from charger output 
terminal. If ground fault on charger clears, problem may be on external DC loads, 

battery, or wires. If ground fault is still present on charger, contact La Marche 

Service Department for further troubleshooting. 

 

Ordering Replacement Parts 

Contact La Marche to place an order for spare or replacement parts.

 

To order replacement parts; please provide 

the model and serial number of the charger, the part needed, and the quantity required. 

Summary of Contents for A39DS

Page 1: ...on and Operation Manual This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com 106 Bradrock Dr Des Plaines 60018 1967 Tel 847 299 1188 F...

Page 2: ...me in contact with any internal components Do not operate this charger outside the input and output ratings listed on the charger nameplate Do not use this charger for any purpose not described in the...

Page 3: ...ger sent back for evaluation and repair CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for any physical damages rep...

Page 4: ...1 Wall Mounting the A39DS 6 Enclosure Only 5 2 1 2 Floor Mounting the A39DS All Enclosures 6 2 2 AC Input Connections 6 2 3 DC Output Connections 8 2 4 Alarms 9 2 4 1 Understanding the Alarms Statuse...

Page 5: ...16 4 3 Reset Alarms 16 4 4 Last 10 Events 16 4 5 Manual Start Zero Volt Battery Start 16 5 Service 17 5 1 Performing Routine Maintenance 17 5 2 Troubleshooting Procedure 18 5 3 Troubleshooting Chart...

Page 6: ...ge when the battery is connected The current limit automatically defaults to 10 of the rated output and the charger timer defaults to 8 hours on start up The A39DS will Auto start upon connection of t...

Page 7: ...s To enter a submenu use the ENTER button The BACK button returns to the previous menu When making a selection the ENTER button will store the value and step back The BACK button will not save the cha...

Page 8: ...nd weight of the A39DS charger Refer to the tables below Output Voltage Frequency Ampere Rating 20 ADC 30 ADC 40 ADC 60 ADC 30 VDC 60 Hz 6 Case 175 lbs 79 4 kg 60 VDC 6 Case 130 lbs 59 kg 6 Case 190 l...

Page 9: ...convection cooling so a clearance of at least 6in 152mm of free air must be maintained on the top bottom and both sides for cooling air Maintain 36in 914mm or more of clearance at the front of the ch...

Page 10: ...times Secure the charger on bolts add appropriate mounting hardware and tighten securely Refer to the figures below for mounting dimensions and specifications NOTE All below dimensions are in inches...

Page 11: ...the floor Place the charger on the bolts add appropriate mounting hardware onto the floor mounting anchor bolts and tighten securely Refer to Figure 2 for hardware specifications and floor mounting di...

Page 12: ...lti tap charger is set for 120VAC input configuration feeder breaker should be double the size of the AC protection 120VAC configured multi tap chargers use both breaker poles in parallel Breaker Size...

Page 13: ...ents Calculating Current Carrying Capacity of Wire Table 5 Wire Size Area Table NOTE These are recommended sizes per La Marche Standards The National Electrical Code NEC and Local Wiring Codes must be...

Page 14: ...V The 60V model has a maximum output voltage setting of 60V The 90V model has a maximum output voltage setting of 90V The 150V model has a maximum output voltage setting of 150V NOTE All alarms automa...

Page 15: ...tput 10 above the reading The current limit will be set to 10 as the default The charger will slowly ramp up to the target voltage this can take up to 10 seconds Charging LED will be lit 3 1 3 Setting...

Page 16: ...nal features Figure 3 A39DS Front Panel The parameters viewable on the idle display are as follows Standard A39DS Display Sequence System DC Outputs Elapsed Time Logging Status Timer Setting Charger C...

Page 17: ...the Settings Menu If YES is selected the display will read Saving Settings the menu will be exited and settings saved If NO is selected the user is prompted to Exit without Saving From this screen if...

Page 18: ...tting or BACK to cancel Elapsed Time The Elapsed Time defaults to 8 hours on start up The charging time increments by 1 hour Select Elapsed Time and press then ENTER button Press the UP and or DOWN bu...

Page 19: ...dvanced Security Password Enable Select YES and enter 0000 Navigate to Set Password Set password to desired four digit pin Make sure to save this new number as it will be necessary to access the menu...

Page 20: ...umber will have to be set via calibration In order to change the serial number used by the software select Serial Number from the Settings menu and press the ENTER button Each digit of the serial numb...

Page 21: ...ttery Start The Manual Start menu allows the user to start the charger when the battery voltage is lower than the minimum detection voltage This feature should only be utilized 1 when the battery is d...

Page 22: ...l number and serial number Yearly 1 Confirm air vents are open Remove dust and debris from interior of unit 2 Verify all connections are tight 3 Perform a visual inspection on all internal components...

Page 23: ...he field La Marche Service Technicians are available to help with troubleshooting or with scheduling charger service When calling for a service inquiry or for troubleshooting assistance be sure to hav...

Page 24: ...Running Hot Inadequate Ventilation Ambient is Too Hot Battery Temperature Too High Insufficient Cool Down Between Charges Battery Power Demand Too Great Battery Needs to be Equalized Erratic Operatio...

Page 25: ...P368SBLxx xxxxxx Update Firmware Enter Password 0000 Update Firmware Yes No LCD Settings LCD Backlight Always ON AUTO OFF 2 mins Serial Number xxxxxx xx Set Clock Set Clock xx xx xxxx xx xx xx Reset C...

Page 26: ...ed and recharge it without clearing any protective devices ENVIROMENTAL Audible Noise Less than 65dBA at any point 5 feet from any vertical surface Operating Temperature 32 to 122 F 0 to 50 C Storage...

Page 27: ...90V BD1 60 90 8 90 240 208 VAC 1 PH 6 300 A39DS 100 90V BD3 100 90 8 90 240 208 VAC 3 PH 8A 350 A39DS 150 90V BD3 150 90 8 90 240 208 VAC 3 PH 8A 565 A39DS 200 90V BD3 200 90 8 90 240 208 VAC 3 PH 72...

Page 28: ...23 Appendix D Document Control and Revision History Part Number 148973 Instruction Number P25 LA39DS 1 Issue ECN 23419 10 23...

Reviews: