background image

 

2.2 

AC Input Connections 

Before beginning any work inside the charger, ensure the following: 

 

Verify all incoming AC supply is de-energized.  

 

Verify that no voltage is present inside the case by using a voltmeter at all input and output terminals.  

 

Check that the source voltage and frequency match the charger front nameplate specifications. 

 

Confirm if charger is multi or single input by referring to charger nameplate.  

 

If charger is confirmed to be a multi-input charger, refer to corresponding charger schematic or AC input 

wiring chart inside charger for transformer tap settings.

 

Select wire size using the table below. This is

 

based on an overload 

current of 110-115%

 of the input current 

listed on the charger nameplate.

 

NOTE:

 Feeder breaker should be sized to match the size of the AC protection used in charger. If multi-tap charger 

is set for 120VAC input configuration, feeder breaker should be double the size of the AC protection. 120VAC 

configured multi-tap chargers use both breaker poles in parallel. 

Breaker Size/ 

Fuse Size - Amps 

AWG Minimum Wire Size Requirement 

for Customer Connection  

AWG Minimum Wire Size 

for Equipment Grounding 

#14 

#14 

#14 

#14 

10 

#14 

#14 

15 

#14 

#14 

20 

#12 

#12 

25 

#10 

#12 

30 

#10 

#10 

40 

#8  

#10 

50 

#8  

#10 

60 

#6 

#10 

70 

#6 

#8  

80 

#4 

#8  

90 

#4 

#8  

100 

#4  

#8  

125 

#2 

#6 

150 

#1 

#6  

175 

#1/0 

#6 

200 

#2/0 

#6  

250 

#4/0  

#4 

300 

250 MCM  

#4 

400 

400 MCM 

#2 

500 

600 MCM 

#2 

Table 4 – AC/DC & Ground Wire Size Minimum Requirements 

(All wires specified in the table are rated at 90 °C or 194 °F) 

 

NOTE:

 These are recommended sizes per La Marche Standards. The National Electrical Code (NEC) and Local 

Wiring Codes must be followed. 

AC Connection Procedure 

First, connect an adequate earth ground lead (use table above for sizing) to the terminal marked ground. Install 

the  input  AC  cables  to  the  AC  input  terminals  of  the  charger.  Refer  to  the  schematic  diagram  for  AC  input 

connections. 

Summary of Contents for A39DS

Page 1: ...on and Operation Manual This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com 106 Bradrock Dr Des Plaines 60018 1967 Tel 847 299 1188 F...

Page 2: ...me in contact with any internal components Do not operate this charger outside the input and output ratings listed on the charger nameplate Do not use this charger for any purpose not described in the...

Page 3: ...ger sent back for evaluation and repair CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for any physical damages rep...

Page 4: ...1 Wall Mounting the A39DS 6 Enclosure Only 5 2 1 2 Floor Mounting the A39DS All Enclosures 6 2 2 AC Input Connections 6 2 3 DC Output Connections 8 2 4 Alarms 9 2 4 1 Understanding the Alarms Statuse...

Page 5: ...16 4 3 Reset Alarms 16 4 4 Last 10 Events 16 4 5 Manual Start Zero Volt Battery Start 16 5 Service 17 5 1 Performing Routine Maintenance 17 5 2 Troubleshooting Procedure 18 5 3 Troubleshooting Chart...

Page 6: ...ge when the battery is connected The current limit automatically defaults to 10 of the rated output and the charger timer defaults to 8 hours on start up The A39DS will Auto start upon connection of t...

Page 7: ...s To enter a submenu use the ENTER button The BACK button returns to the previous menu When making a selection the ENTER button will store the value and step back The BACK button will not save the cha...

Page 8: ...nd weight of the A39DS charger Refer to the tables below Output Voltage Frequency Ampere Rating 20 ADC 30 ADC 40 ADC 60 ADC 30 VDC 60 Hz 6 Case 175 lbs 79 4 kg 60 VDC 6 Case 130 lbs 59 kg 6 Case 190 l...

Page 9: ...convection cooling so a clearance of at least 6in 152mm of free air must be maintained on the top bottom and both sides for cooling air Maintain 36in 914mm or more of clearance at the front of the ch...

Page 10: ...times Secure the charger on bolts add appropriate mounting hardware and tighten securely Refer to the figures below for mounting dimensions and specifications NOTE All below dimensions are in inches...

Page 11: ...the floor Place the charger on the bolts add appropriate mounting hardware onto the floor mounting anchor bolts and tighten securely Refer to Figure 2 for hardware specifications and floor mounting di...

Page 12: ...lti tap charger is set for 120VAC input configuration feeder breaker should be double the size of the AC protection 120VAC configured multi tap chargers use both breaker poles in parallel Breaker Size...

Page 13: ...ents Calculating Current Carrying Capacity of Wire Table 5 Wire Size Area Table NOTE These are recommended sizes per La Marche Standards The National Electrical Code NEC and Local Wiring Codes must be...

Page 14: ...V The 60V model has a maximum output voltage setting of 60V The 90V model has a maximum output voltage setting of 90V The 150V model has a maximum output voltage setting of 150V NOTE All alarms automa...

Page 15: ...tput 10 above the reading The current limit will be set to 10 as the default The charger will slowly ramp up to the target voltage this can take up to 10 seconds Charging LED will be lit 3 1 3 Setting...

Page 16: ...nal features Figure 3 A39DS Front Panel The parameters viewable on the idle display are as follows Standard A39DS Display Sequence System DC Outputs Elapsed Time Logging Status Timer Setting Charger C...

Page 17: ...the Settings Menu If YES is selected the display will read Saving Settings the menu will be exited and settings saved If NO is selected the user is prompted to Exit without Saving From this screen if...

Page 18: ...tting or BACK to cancel Elapsed Time The Elapsed Time defaults to 8 hours on start up The charging time increments by 1 hour Select Elapsed Time and press then ENTER button Press the UP and or DOWN bu...

Page 19: ...dvanced Security Password Enable Select YES and enter 0000 Navigate to Set Password Set password to desired four digit pin Make sure to save this new number as it will be necessary to access the menu...

Page 20: ...umber will have to be set via calibration In order to change the serial number used by the software select Serial Number from the Settings menu and press the ENTER button Each digit of the serial numb...

Page 21: ...ttery Start The Manual Start menu allows the user to start the charger when the battery voltage is lower than the minimum detection voltage This feature should only be utilized 1 when the battery is d...

Page 22: ...l number and serial number Yearly 1 Confirm air vents are open Remove dust and debris from interior of unit 2 Verify all connections are tight 3 Perform a visual inspection on all internal components...

Page 23: ...he field La Marche Service Technicians are available to help with troubleshooting or with scheduling charger service When calling for a service inquiry or for troubleshooting assistance be sure to hav...

Page 24: ...Running Hot Inadequate Ventilation Ambient is Too Hot Battery Temperature Too High Insufficient Cool Down Between Charges Battery Power Demand Too Great Battery Needs to be Equalized Erratic Operatio...

Page 25: ...P368SBLxx xxxxxx Update Firmware Enter Password 0000 Update Firmware Yes No LCD Settings LCD Backlight Always ON AUTO OFF 2 mins Serial Number xxxxxx xx Set Clock Set Clock xx xx xxxx xx xx xx Reset C...

Page 26: ...ed and recharge it without clearing any protective devices ENVIROMENTAL Audible Noise Less than 65dBA at any point 5 feet from any vertical surface Operating Temperature 32 to 122 F 0 to 50 C Storage...

Page 27: ...90V BD1 60 90 8 90 240 208 VAC 1 PH 6 300 A39DS 100 90V BD3 100 90 8 90 240 208 VAC 3 PH 8A 350 A39DS 150 90V BD3 150 90 8 90 240 208 VAC 3 PH 8A 565 A39DS 200 90V BD3 200 90 8 90 240 208 VAC 3 PH 72...

Page 28: ...23 Appendix D Document Control and Revision History Part Number 148973 Instruction Number P25 LA39DS 1 Issue ECN 23419 10 23...

Reviews: