4.1.1 Output Settings
The Output Settings submenu provides access to change the DC Voltage, DC Current Limit as well as the Elapsed
Time.
DC Voltage Setting
The DC voltage is automatically set once the battery voltage is detected. The DC voltage increments by 0.1V.
Select “DC Voltage” and then press ENTER button. Press the UP and/or DOWN buttons until the desired voltage
level is displayed. Press ENTER to store the setting or BACK to cancel.
à
DC Current Limit Setting
The DC current limit automatically defaults to 10% of the rated output. The DC current limit increments by 1%.
Select “DC Current Limit” and then press ENTER button. Press the UP and/or DOWN buttons until the desired
current limit level is displayed. Press ENTER to store the setting or BACK to cancel.
à
Elapsed Time
The Elapsed Time defaults to 8 hours on start-up. The charging time increments by 1 hour. Select “Elapsed Time”
and press then ENTER button. Press the UP and/or DOWN buttons until the required charging time is displayed.
Press ENTER to store the setting or BACK to cancel.
à
4.1.2 Alarm Settings
The Alarm Settings submenu provides access to the change the Alarm Thresholds. The Alarm Thresholds setting
allows the user to determine the current or voltage value at which an alarm trigger. The threshold can be changed
for the following:
•
Low DC Current
à
NOTE:
Alarm threshold defaults are based on the charger rating. The alarm threshold values shown above are
not representative of the default values for any specific A39DS charger.
>DC Voltage
DC Current Lim.
DC Voltage
130.2 V
>DC Current Lim.
Elapsed Time
DC Current
10 Percent
>Elapsed Time
DC Voltage
Elapsed Time
8 Hours
>Alarm Settings
Low DC Current
Alarm 0.5 A