3
1.1
Storing the A39DS
If the A39DS is to be stored for more than a few days after delivery, it should be stored within its shipping
container. The location chosen for storage should be within an ambient temperature of -40 to 185° F (-40 to 85°
C) with a non-condensing relative humidity of 0 to 95%.
NOTE:
Storage should not exceed 2 years due to the limited shelf life of the DC filter capacitors when they are
not in service.
1.2
Moving the A39DS
After careful inspection and upon verification that the A39DS is undamaged, identify the enclosure style and
weight of the A39DS charger. Refer to the tables below.
Output
Voltage
Frequency
Ampere Rating
20 ADC
30 ADC
40 ADC
60 ADC
30 VDC
60 Hz
6 Case
175 lbs.
(79.4 kg)
60 VDC
6 Case
130 lbs.
(59 kg)
6 Case
190 lbs.
(86.2 kg)
90 VDC
6 Case
300 lbs.
(136.1 kg)
150 VDC
6 Case
300 lbs.
(136.1 kg)
Table 1 – Case Type and Weight (Single Phase, 20-60 ADC)
Output
Voltage
Frequency
Ampere Rating
50 ADC
100 ADC
150 ADC
200 ADC
60 VDC
60 Hz
8A Case
325 lbs.
(147.4 kg)
8A Case
350 lbs.
(158.8 kg)
72 Case
450 lbs.
(204.1 kg)
90 VDC
8A Case
350 lbs.
(158.8 kg)
8A Case
565 lbs.
(256.3 kg)
72 Case
637 lbs.
(288.9 kg)
150 VDC
8A Case
345 lbs.
(156.5 kg)
8A Case
600 lbs.
(272.2 kg)
27 Case
640 lbs.
(290.3 kg)
27 Case
690 lbs.
(313 kg)
Table 2 – Case Type and Weight (Three Phase, 50-200 ADC)
1
Equipment Handling