G O M + 표 준 형 - 영 문
58
2.
Exhaust flue connection
Forced Exhaust type exhaust flue top connected to the common exhaust flue
should be blocked at the top and the surrounding area are open.
When the distance from the opening of the common exhaust flue top to the boiler
reverse current guard opening bottom is less than 4m, install a separate exhaust flue.
3.
Common Exhaust duct top
Common exhaust duct top must be installed at least 1.5m higher than the highest
point of the roof such as the water thank.
Common exhaust duct top must not be installed on the wind pressure area.
Effective cross section of the common exhaust duct top opening must be greater
than the effective cross section of the common exhaust duct.
Do not install an electric fan on the common exhaust duct top. If a manual fan is
necessary, the cross section of the fan should be larger than the cross section of
the common exhaust duct.
4.
Caution
The number of boilers connected on the same floor should be limited to two.
Do not connect together with other fuel boilers such as coal or oil boilers.
Do not connect forced exhaust flue type and conventional flue type of boilers together.
There should be no objects that obstruct the exhaust gas flow such as fireproof
damper inside the common exhaust duct and a cleaning drainage and water
drainage should be installed at the bottom.
When installing condensing model to the common exhaust duct, it must be structured
to prevent any absorption of condensed water inside of the common exhaust duct.