11.5. 230V
AC
O
UTPUT
P
ROTECTIONS
11.5.1 Overload
I
OVERLOAD
18
±
0.5 A
RMS
When protection takes place the
inverter switches off automatically.
Before restarting the inverter it is
preferable to detach all appliances.
The protection curve, shown in Figure
12, informs about the transitory time
before protection intervention.
11.5.2 Output Current Limiter
I
MAX
32 A
RMS
±
5%
Output current is reduced if exceeding
the indicated threshold. Output
voltage remains sinusoidal till peak
current limiter threshold is reached.
11.5.3 Short Circuit on Output
Inverter switches off automatically.
Before restarting the inverter it is
preferable to detach all appliances.
11.5.4 Peak Current Limiter
Threshold
50 A ± 10%
Inverter clips the output current in
order to keep the absolute peak value
inside a safety region.
11.5.5 Maximum Output
Current Derating
-0.8 A
RMS
/°C
When temperature overcomes the
fixed threshold of 55±5°C on the heat
sink temperature test point, the
inverter reduce the Maximum Output
Current value (I
MAX
).
11.5.6 Over Temperature
70
±
5 °C
When temperature overcomes the
fixed threshold of 70±5°C on the heat
sink temperature test point, the
inverter switches off automatically.
Before restarting the inverter it is
preferable to detach all appliances.
11.5.7 Output Undervoltage
due to Insufficient Input
Voltage
2
(+5/-0)%
After 5 sec. unit trips without
overload
conditions
(stand-by
condition) due to low BUS
voltage. Auto-restart function
when normal operative conditions
turn back.
11.5.8 Output Undervoltage
due to Severe Overload
100 V
RMS
± 5%
Unit trips immediately when peak
current limiter is working.
Before restarting the inverter it is
preferable to detach all appliances.
11.5.9 Output Undervoltage
due to not Severe
Overload
180 V
RMS
± 5%
Unit trips after 6 sec.
Before restarting the inverter it is
preferable to detach all appliances.
11.5.10 Pre Test at Starting
Before starting the inverter, controls if
measurable input conditions are inside
tolerance (see 11.2).
MANUAL
EFU10000
4.0kVA INVERTER UNIT
Pag. 26
/ 34
207V
RMS
2
Output voltage till 207V
RMS
shall be sinusoidal, without clipping, a part from situations when current limiter is
working.