POSITION
ON CON6
DESCRIPTION
VOLTAGE
VALUE
1
RL2 NORMALLY CLOSED
N.A.
2
RL2 COMMON
N.A.
3
RL2 NORMALLY OPEN
N.A.
4
GENERIC
0/12V
DC
5
12V
DC
OUTPUT
12V
DC
6
12V
DC
OUTPUT
0V
DC
MANUAL
EFU10000
4.0kVA INVERTER UNIT
Pag. 14
/ 34
4.6 R
ELAY
C
ONNECTOR
A 6 ways auxiliary connector (named CON6) is available.
It provides the contacts of an integrated relay, named RL2
1
, a generic signal output, together with a
12V
DC
– 400mA insulated power supply.
Its lay-out is shown on Figure 10, while the signals reference is listed on Table 2.
NOTE
For connecting CON7 use only counterpart Hirose DF1B-10S-2.5R with
proper terminals.
1 2 3
4 5 6
Figure 10: CON6 connector lay-out
CONTACT
CONTACT
CONTACT
OUTPUT (SIGNAL)
INSULATED
INSULATED GROUND
Table 2: Signals on CON7 connector
4.7 B
RAKE
R
ESISTOR
C
ONNECTORS
The customer shall connects to the two proper M6 studs an external brake resistor with a nominal
value of 40 ±10%.
4.8 CON4 & CON5
Connectors reserved to KWG for programming and diagnostic.
1
Relay RL2 nominal specification: 6A - 250V
AC
– Maximum power 250VA (AC 15).