EG3002
3
SECTION 4 : POTENTIOMETER ADJUSTMENTS AND DIP SWITCH FUNCTIONS
DIP Switch Functions
SW 1 to 4
:
Frequency Range Selection
SW 5 ON
:
Cummins PT PUMP
SW 6 ON
:
Extreme Slow Response engines
IDLE SPEED
:
IDLE Speed
Setting
When Terminals 2 & 3
shorted, use this pot to
adjust IDLE speed.
RUN SPEED
:
Operating
Speed Setting
10
、
11
:
MPU Input
Use shielded cable
6
、
7
、
9
:
Remote Speed Potentiometer
Connect a 5 K
Ω
potentiometer. Must use shielded
cable.
6
、
8
:
Isochronous Load Sharing (ILS) Input
Analog input signal from the load sharing controller.
Must be isolated from battery power. Terminal 6 is
ground of load sharing controller. Terminal 8 is
input signal from controller.
1
、
2
:
Battery Input
Connect to genset battery.
Use14 AWG wire or larger
3
:
IDLE Control Contact
When shorted to terminal 2 unit
will go to IDLE state.
4
、
5
:
Output to Actuator
Use 14 AWG wire or larger
INT
:
Integral Setting
DIF
:
Differential Setting
DROOP
:
Speed Droop
Setting
GAIN
:
Gain Setting
RAMP
:
Ramp Time
Time for engine speed to climb from IDLE to
operating speed. (3 to 20 seconds)
DROOP
DIF.
INT.
GAIN
RAMP
SW1-ON 600~1200HZ
SW2-ON 1200~2500HZ
SW4-ON 5000~9500HZ
SW3-ON 2500~5000HZ
POWER : DC12/24V
IDLE
1
2
3
ACT
4
5
6
7
MPU
9
ILS
8
10
11
~
+
REMOTE
SPEED POT
RUN SPEED
IDLE SPEED
SW5-ON PT-PUMP
EG3002
+
SW6-ON Slow response
SW