background image

 

___________________________________________________________________________________________ 

EG3002

 

SECTION 6 : ADJUSTMENT 

6.1 

Initial Settings Before Trial Run 

 
6.1.1  With the engine OFF toggle the actuator linkage 

back and forth. The movement should be smooth 
with  no  gap  in  the  linkage  connection  to  the 
actuator. If there is a gap it will make it difficult to 
achieve stable settings. 

 
6.1.2  Frequency Range Selection 
 

Frequency  range  is  selected  according  to  the 
frequency  of  the  signal  sent  by  the  magnetic 
pickup (MPU) at desired operating speed. 

 

MPU frequency = 

RPM 

×

  Flywheel teeth 

60 seconds 

 

Frequency Range Selection 

SW-1 ON 

  600 

 1200 Hz 

SW-2 ON 

1200 

 2500 Hz 

SW-3 ON 

2500 

 5000 Hz 

SW-4 ON 

5000 

 9500 Hz 

 

NOTICE 

Only one DIP SW 1 – 4 can be turned ON. 

 
If  the  number  of  flywheel  teeth  is  not  known  then  test 
each setting one by one from lowest (SW-2) to highest 
(SW-4). 
 
6.1.3  Moving  SW-5  to  ON  decreases  the  gain  of  the 

controller  for  use  with  Cummins  PT-PUMP  type 
or low-impedance, built-in actuators. 

 
6.1.4  VR Settings 

 

Run Speed

Turn counterclockwise to minimum. 

 

IDLE  Speed

Turn  clockwise  to  maximum  (If 

Cummins PT-PUMP type adjust counterclockwise 
to minimum). 

 
Set all other values according to diagram below : 

DROOP

DIF.

INT.

GAIN

RAMP

SW

 

 
If  an  external  VR  is  used  then  adjust  to  a  middle 
position. 
 
Open the IDLE switch between terminals 2 & 3. 
 
 
 

NOTICE 

RUN  SPEED  and  IDLE  SPEED  VR  are  25  turn 
precision  potentiometers.  When  adjusted  past 
minimal  or  maximum  will  begin  to  make  a 
clicking sound but will not be damaged.
 

 
6.2 

Trial Run 

 
6.2.1  Engine will not start 
 

Refer  to  Section  7.1  Troubleshooting  below  for 
possible  causes.  If  the  engine  still  will  not  start 
normally  then  increase  Run  Speed  setting  or 
Frequency  Range  SW  setting  to  a  higher  range 
(Run  Speed  should  be  set  to  minimum  at  this 
time) 

 
6.2.2  If  engine  starts  normally  then  slowly  adjust  Run 

Speed to the target speed. If unable to adjust to 
the target speed then set Frequency Range SW 
to next higher level. (Run Speed should be set to 
minimum at this time) 

 
6.2.3  If  the  engine  goes  directly  to  over  speed  after 

starting then adjust the Frequency Range SW to 
the next lower level. 

 

NOTICE 

When  conducting  a  trial  run  it  is  possible  the 
engine  speed  cannot  be  controlled.  Therefore,  it 
is recommended to install an additional device to 
shutdown the engine, such as a fuel valve switch.
 

 
6.3 

IDLE Speed and Ramp Time Settings 

 
6.3.1  With the engine running at operating speed short 

Terminals  2  and  3.  Engine  speed  will  drop  to 
IDLE speed at this time. 

 
6.3.2  Adjust  IDLE  Speed  counterclockwise  to  the 

desired IDLE level. 

 
6.3.3  RAMP  time  too  long  it  could  cause  the  GCU  to 

activate the under speed protection function. 

 

RAMP  time  too  short  could  lead  to  incomplete 
combustion of fuel. 

 
6.3.4  Open  the  connection  between  Terminals  2  &  3. 

Engine  speed  will  climb  from  IDLE  speed  to 
operating  speed.  If  RAMP  time  is  inappropriate 
then short Terminals 2  &  3 again  and adjust the 
RAMP.  Repeat  this  step  until  setting  is 
appropriate. 

 
6.3.5  Stop the engine then start again. If the engine will 

not start then adjust the IDLE Speed clockwise to 
increase the IDLE setting. 

 

Summary of Contents for EG3002

Page 1: ...06037 Taiwan EG3002 Electronic Engine Governor Controller User Manual Engine Start Smoke Limiting function IDLE Speed Setting For External Built in and PT Pump type actuators Newly added extreme slow response engine setting All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ... 10 000 Hz Voltage 1 120 Vac RMS Speed Temperature Shift Less than 3 at temperature range 40 to 80 C Frequency Adjustment Speed Adjustment pot 25 turn Environment Setting range 600 9 500 Hz With DIP Switch Operating Temperature 40 to 80 C Storage Temperature 40 to 85 C Remote Speed Potentiometer Terminals 6 7 9 Relative Humidity Max 95 Max 7 5 KΩ 1 watt potentiometer Vibration 5 5Gs 60 Hz Isochron...

Page 3: ...signal from the load sharing controller Must be isolated from battery power Terminal 6 is ground of load sharing controller Terminal 8 is input signal from controller 1 2 Battery Input Connect to genset battery Use14 AWG wire or larger 3 IDLE Control Contact When shorted to terminal 2 unit will go to IDLE state 4 5 Output to Actuator Use 14 AWG wire or larger INT Integral Setting DIF Differential ...

Page 4: ...N Slow response SW R 3 1 2 1K 3 1 2 CCW CW ATTENTION 1 The unit must be installed by qualified technical personnel Improper installation wiring or settings could lead to injury to personnel and or damage to equipment 2 This unit has no Over Speed Protection function It is recommended to install a separate over speed protection device 3 The battery connects directly to the controller with a fuse fo...

Page 5: ...ill begin to make a clicking sound but will not be damaged 6 2 Trial Run 6 2 1 Engine will not start Refer to Section 7 1 Troubleshooting below for possible causes If the engine still will not start normally then increase Run Speed setting or Frequency Range SW setting to a higher range Run Speed should be set to minimum at this time 6 2 2 If engine starts normally then slowly adjust Run Speed to ...

Page 6: ... until optimal settings are achieved 3 Engine speed instability can be divided into slow oscillations once every 2 to 5 seconds and rapid oscillations 2 to 8 times per second slow oscillation is usually because GAIN is too low and or INT is too high Rapid oscillations however can occur in two ways 4 2 4 times per second GAIN setting too high 4 8 times per second DIF setting too high 6 5 Remote Spe...

Page 7: ...e then replace the MPU During engine start confirm that the input voltage to Terminals 10 11 is greater than 1 Vac If less than 1 Vac check the gap between the tip of the MPU and the flywheel teeth The distance should be 0 037 mm to 0 127 mm 3 Actuator fault failed disconnected etc 3 If the two items above are both normal then check whether Terminals 4 5 have a voltage output during cranking If th...

Page 8: ...hether MPU is disconnected Must be directly connected to Terminals 10 11 Resistance of 10 1 000Ω is normal Check that MPU has been connected with shielded wire grounded at one end Repair wiring as required 4 Controller defective 4 With engine OFF apply power to the controller if actuator linkage moves or if there is a voltage output on Terminals 4 5 this indicates the controller is defective 7 4 E...

Reviews: